EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Lab view <-> EPICS
From: "David H. Thompson" <[email protected]>
To: "Mark M. Ito" <[email protected]>
Cc: techtalk <[email protected]>
Date: Wed, 21 Aug 2002 10:47:29 -0400
Mark,

I am currently in the process of testing a shared memory approach to this
problem.  What we are doing is using a dll to implement an interface to a
shared memory database.  With this is an IOC that runs with labView on
windows.  The shared memory is configured by the IOC from the IOC's database
when it starts up and then labView can access the variables in the shared
memory database by loading the dll. There is device support for
ai,ao,longin,longout and waveform (in).  The in-memory data types can be
long, float, or double for any of the supported record types.  I also have
implemented a means to simulate interrupts across the dll, pass time stamps
with the interrupts, and buffer the data so that the IOC can run
asynchronously with labView. The buffering is what I am testing now.

If interested, let me know and we can see how to share this, admittedly it
is very "alpha" right now.


> -----Original Message-----
> From: Mark M. Ito [mailto:[email protected]]
> Sent: Wednesday, August 21, 2002 10:23 AM
> To: EPICS tech-talk
> Cc: Jarreas Underwood
> Subject: Labview <-> EPICS
>
>
> Tech Talkers,
>
> I need some guidance on how to get Labview variables incorporated in a
> separate data-recording stream. The data acquisition system in question is
> EPICS-aware; we can read any PV that is out there on the network. The
> problem is getting the Labview application to present its data to the
> EPICS world.
>
> My guess is that the best thing going now is described at:
>
>   http://mesa53.lanl.gov/lansce8/Epics/ActiveXCAServer/default.htm
>
> but since that is only a guess, I would like to hear other opinions.
>
> Thanks in advance.
>
>   -- Mark
>
> --
> Mark M. Ito, Thomas Jefferson National Accelerator Facility
> 12000 Jefferson Ave., Mail Stop 12H, Newport News, VA 23606
> Email: [email protected], Phone: (757)269-5295
> WWW: http://claspc2.jlab.org
>


References:
Labview <-> EPICS Mark M. Ito

Navigate by Date:
Prev: Re: subRecord fix Andrew Johnson
Next: HP Lan-GPIB gateway stein
Index: 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Labview <-> EPICS Mark M. Ito
Next: Siemens/Profibus Drivers Robby Tanner
Index: 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·