It's TSR# 453418.
I don't send copies of the files around. They are property of WRS. It is
[email protected] who sent them to SLS. Unfortunately, he
didn't add a revision number to the files when he changed them recently. So,
the latest revision entries in the files are
dec21x40End.h 22sep03,mni added BOOL restarting member to
DEC21X40_DRV_CTRL structure
dec21x40End.c 22sep03,mni added fix for SPR# 84658
Please check with Mr Niedermair if he did essential changes since.
Kind regards,
Andy
----------------------------------
Andreas Isenegger
SLS Controls
Paul Scherrer Institute, WSLA/207
CH-5232 Villigen PSI, Switzerland
Tel/Fax: ++41 (56) 310 5125/4413
----------------------------------
----- Original Message -----
From: "Ernest L. Williams Jr." <[email protected]>
To: "Andreas Isenegger" <[email protected]>
Cc: "EPICS tech-talk" <[email protected]>
Sent: Thursday, September 29, 2005 12:55 AM
Subject: Re: VxWorks5.5 on MVME230x doesn't reestablish broken N/W link
On Wed, 2005-09-28 at 17:12 +0200, Andreas Isenegger wrote:
Hello All,
Since I posted 2 e-mails in July 2005 seeking for help, I thought it
would
be worth informing you that the problem could be solved.
There are indeed some bugs in Wind River's N/W driver (dec21x40End.h/c)
that
cause the misbehavior of the IOC. I got new revisions of these files from
Martin Niedermair, WRS Austria, which solve the issue. Strangely enough,
a
different support engineer of WRS sent me another revision of the same
files, which doesn't fix the bug. About 2 years back, they were
branched...
. The latest official patch from WRS contains again different revisions
of
the files.
Thus, if you are experiencing troubles with IOC's disconnecting for 'no
reasons', or reset ports of N/W switches to regain links to IOC's, build
a
new VxWorks image with the latest revision of these files.
Can you send us a copy of the files or give us a rev. number to compare
against?
I think we are fine but I want to double-check.
Our MVME2101s also use the "dec21x40End.h/c"
PS: Did WRS give you a TSR or SPR that we could look up on our end?
Thanks,
Ernest L. Williams Jr.
SNS Control Systems Group
ORNL
Kind regards,
Andreas Isenegger
----------------------------------
Andreas Isenegger
SLS Controls
Paul Scherrer Institute, WSLA/207
CH-5232 Villigen PSI, Switzerland
Tel/Fax: ++41 (56) 310 5125/4413
----------------------------------
- References:
- VxWorks5.5 on MVME230x doesn't reestablish broken N/W link Andreas Isenegger
- Re: VxWorks5.5 on MVME230x doesn't reestablish broken N/W link Ernest L. Williams Jr.
- Navigate by Date:
- Prev:
Re: VxWorks5.5 on MVME230x doesn't reestablish broken N/W link Ernest L. Williams Jr.
- Next:
RE: VxWorks TIMEZONE hack, anyone? Rees, NP (Nick)
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: VxWorks5.5 on MVME230x doesn't reestablish broken N/W link Ernest L. Williams Jr.
- Next:
TSconfigure documentation Denison, PN (Peter)
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|
ANJ, 02 Sep 2010 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|