Experimental Physics and Industrial Control System
>> is there another location
Depends on your setup of course but I see something like this in my arch.log right at the beginning.
<context class="com.cosylab.epics.caj.CAJContext">
<preemptive_callback>true</preemptive_callback>
<addr_list>gateway:5076 gateway:5077 gateway:5078 other-gateway:5064</addr_list>
<auto_addr_list>false</auto_addr_list>
<connection_timeout>30.0</connection_timeout>
<beacon_period>15.0</beacon_period>
<repeater_port>5069</repeater_port>
<server_port>5076</server_port>
<max_array_bytes>80000000</max_array_bytes>
<event_dispatcher class="org.epics.archiverappliance.engine.epics.JCAEventDispatcherBasedOnPVName"/>
</context>
>> pause/resume I tried
Pausing/resuming tears down and recreates the CAJ channel for the PV so if you are unable to connect even after this you probably have some misconfiguration; that is, you can rule out most transient errors.
>> IOC's log on ioc machine right
Yes; sometimes there could be stuck tasks on the IOC side; you can check for that.
Your PV Details page for this PV could have information there that could help. You can get to this using something like so - http://localhost:17665/mgmt/bpl/getPVDetails?pv=Your_PV
Finally, would you be in a position to attempt a restart?
Regards,
Murali
________________________________________
From: Gabriel de Souza Fedel <[email protected]>
Sent: Friday, September 1, 2017 10:52 AM
To: Shankar, Murali; [email protected]
Cc: ([email protected])
Subject: Re: Archiver: Problems with disconnected PVs
Em 01-09-2017 13:39, Shankar, Murali escreveu:
>>> This seems like it might be a CA client configuration issue
>
> This is the most likely case. The engine prints out it's CAJ
> configuration on startup and you should be able to see this in your logs.
>
I didn't find it. I find engine/logs/catalina.err, is there another
location?
>
> You can try a couple of things. You can pause/resume the PV's in
> question and see if they reconnect back. You can also look in the IOC's
> logs and see if there is anything interesting going there.
>
pause/resume I tried. IOC's log on ioc machine right? apparently there
is no errors (on epics console).
>
> Regards,
Regards and thank you for the answer
>
> Murali
>
>
--
Gabriel Fedel
Software de Operação das Linhas de Luz
Laboratório Nacional de Luz Síncrotron – (LNLS)
Centro Nacional de Pesquisa em Energia e Materiais (CNPEM)
[email protected] | +55 (19) 3512 1226
www.lnls.cnpem.br
- Replies:
- Re: Archiver: Problems with disconnected PVs Gabriel de Souza Fedel
- References:
- Re: Archiver: Problems with disconnected PVs Shankar, Murali
- Re: Archiver: Problems with disconnected PVs Gabriel de Souza Fedel
- Navigate by Date:
- Prev:
Re: Archiver: Problems with disconnected PVs Gabriel de Souza Fedel
- Next:
Re: Archiver: Problems with disconnected PVs Gabriel de Souza Fedel
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Archiver: Problems with disconnected PVs Gabriel de Souza Fedel
- Next:
Re: Archiver: Problems with disconnected PVs Gabriel de Souza Fedel
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024