1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 <2012> 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 <2012> 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: .PACT .TIME |
From: | Pavel Maslov <[email protected]> |
To: | "Dalesio, Leo" <[email protected]>, EPICS Tech Talk <[email protected]> |
Date: | Wed, 12 Dec 2012 18:35:13 +0400 |
Login and set the TPRO field to a non zero value.
It will print the name of the record and every passive record processed in this lock set after the record with the TPRO field set to 1.
Or, set the deadband of an AI or CALC to -1. It will post the VAL field each time as the absolute value of the change will exceed it.
From: [email protected] [mailto:[email protected]] On Behalf Of Pavel Maslov
Sent: Wednesday, December 12, 2012 8:39 AM
To: EPICS Tech Talk
Subject: .PACT .TIME
Hi,
Is there a way I can subscribe to these record fields?
I would like to know if my record has been processed.
The record itself is being processed ~30 seconds.
It's strange when I caget record.PACT I can see 1 or 0. However, camonitor doesn't react on the value change whatsoever.
Is there any other way around?
--
Best regards,
Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia
Mobile: +7 (951) 672 22 19
Landline: +7 (812) 461 01 01