1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: DB CA link to PROC field
From: Tim Mooney <[email protected]>
To: Benjamin Franksen <[email protected]>
Cc: [email protected]
Date: Tue, 14 Jul 2009 15:55:23 -0500
Ben, I get that same error message when I use a CA link (from any record) to process a record whose processing results in an error. If your situation is
like mine, OTERMPCGP:colStRmp should be in some kind of alarm.

Tim

Benjamin Franksen wrote:
I get this message on the iocsh (base is 3.14.8.2):

dbCaTask ca_array_put Channel write request failed
OTERMPCGP:cmdRmp has DB CA link to OTERMPCGP:colStRmp.PROC

This is my record definition:

record(seq,"OTERMPCGP:cmdRmp") {
	field(DOL1,"1")
	field(LNK1,"OTERMPCGP:stRmp PP NMS")
	field(DOL2,"1")
	field(LNK2,"ERMPCGP:disableAll PP NMS")
	field(DOL3,"ERMPCGP:setNrg NPP NMS")
	field(LNK3,"ERMPCGP:rdRmp PP NMS")
	field(DOL4,"1")
	field(LNK4,"OTERMPCGP:startRmp.PROC PP NMS")
	field(DOL5,"1")
	field(LNK5,"OTERMPCGP:colStRmp.PROC CA NMS")
}

So... what's the problem?

Cheers
Ben


--
Tim Mooney ([email protected]) (630)252-5417
Beamline Controls & Data Acquisition Group (www.aps.anl.gov/aod/bcda)
Advanced Photon Source, Argonne National Lab


Replies:
Re: DB CA link to PROC field Benjamin Franksen
References:
DB CA link to PROC field Benjamin Franksen

Navigate by Date:
Prev: Re: Agilent E2050 Benjamin Franksen
Next: Re: DB CA link to PROC field Benjamin Franksen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: DB CA link to PROC field Benjamin Franksen
Next: Re: DB CA link to PROC field Benjamin Franksen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·