> I have an application where I want to connect a PP output link (of a
> genSub record) to the VAL field of a passive ao record...
>
> Silly me... I hadn't read the README. You connect to the SLNK field (I had
> thought that you could only connect FLNK to SLNK).
>
================================================================================
>
> I thought you were supposed to link to the SVAL field? (artificial name for
> the VAL field which CAPFAST treats as in IN instead of an OUT)
>
>
> Chip
>
================================================================================
>
> The SVAL port was added to the CEBAF symbols
> but is not provided by the symbols
> currently in use at APS, LANL and by the astronomy
> community. The SLNK port works identically to the SVAL port,
> though using the latter would provide more meaningful documentation.
>
> Rozelle
================================================================================
I've actually done this sort of thing a lot (using a PP link from an OUTLINK
field to a VAL field). My favorite method is to use one of the "large" or
"medium" symbols for the ao record and define one of the "user-defined" input
links (FLD0, FLD1, etc.) to be VAL. The latest versions of e2sr/e2db do not
mind if VAL is defined as both an input and output.
Eric Bjorklund
Los Alamos Neutron Science Center
- Navigate by Date:
- Prev:
Re: Capfast question: linking to ao .VAL field? Rozelle Wright
- Next:
VME: Cannot find record type dfan Marian Zurek
- Index:
1994
1995
<1996>
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Portable Channel Access Server Jeff Hill
- Next:
VME: Cannot find record type dfan Marian Zurek
- Index:
1994
1995
<1996>
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|