Experimental Physics and Industrial Control System
|
On second thought, I may see a problem after all…
mrf-TEST-EVG0:TrigEvt4-Enable-RB Enabled
mrf-TEST-EVG0:TrigEvt4-EvtCode-RB 0
It looks like you are using trigger 4 to send the event, but the event code you are “sending” is 0 — which is the “null” event. I think it should be set to “4” if you want the EVR to see an event 4.
-Bj
|
- References:
- Event triggers for plusers not detected (mrf-timing system) Karim Laihem
- Navigate by Date:
- Prev:
Re: Event triggers for plusers not detected (mrf-timing system) Bjorklund, Eric A
- Next:
modbus: problem on readInt32Array Davide Marcato