1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Problem when formating a field as HEX32
From: "Kasemir, Kay" <[email protected]>
To: Pilar Gil Jaldo <[email protected]>, "[email protected]" <[email protected]>
Date: Tue, 14 Nov 2017 15:16:52 +0000
Hi:

Well, not sure what else could be different.
I'm using the latest SNS version of CSS ('nightly' build from https://ics-web.sns.ornl.gov/css/products.html)
and under Edit, Preferences, CSS Applications, Display, BOY, OPI Runtime I set "PV Connection Layer" to "vtype_pv".

-Kay

________________________________________
From: Pilar Gil Jaldo <[email protected]>
Sent: Tuesday, November 14, 2017 10:10 AM
To: Kasemir, Kay; [email protected]
Subject: Re: Problem when formating a field as HEX32

Thank you, Kay for answering.

It could be that that is part of the problem, but I'm not sure.

In any case, I do not understand why it works with Decimal format type
and not with Hex32. I'm not changing at all the database, it is just a
formatting.

Or maybe am I missing something?

Thank you in advance

Pilar



On 14/11/17 15:01, Kasemir, Kay wrote:
> Hi:
>
> When I try your example with a plain record, bo device support, it works OK:
>
> record(ao, "MaskSet")
> {
>       field(DOL, 255)
>       field(LOPR, 0x00000000)
>       field(HOPR, 0x7FFFFFFF)
>       field(PINI, "YES")
> }
>
> Enter 0xFFFFFF7 -> I get 0xFFFFFF7
> Enter 0xFFFFFF0 -> I get 0xFFFFFF0
> Enter 0x800007F ->  I get 0x800007F
> Enter 0x8000080 -> I get 0x8000080
> Enter FFFFFFFF (no leading '0x') -> I get 0xFFFFFFFF
> 0 -> 0x0
> -1 -> 0xFFFFFFFF
> -7 -> 0xFFFFFFF9
>
> ==> Could your number clamping be caused by the asyn device support that you're using?
>
> -Kay
>
> ________________________________________
> From: [email protected] <[email protected]> on behalf of Pilar Gil Jaldo <[email protected]>
> Sent: Tuesday, November 14, 2017 5:17 AM
> To: [email protected]
> Subject: Problem when formating a field as HEX32
>
> Dear all,
>
> I am having following problem.
>
> MaskSet is a 32 double variable:
>
> record(ao, "$(user):MaskSet")
> {
>       field(DTYP ,"asynInt32")
>       field(OUT  ,"@asyn($(PORT),$(ADDR),$(TIMEOUT))mask")
>       field(LOPR, 0x00000000)
>       field(HOPR, 0x7FFFFFFF)
>       field(PINI, "YES")
> }
>
> For the CSS/BOY,  I have defined a text input field which makes possible
> to change the value of this field.
> When I set "Default" as format type of the field, everything works fine.
> The problem comes when changing the format type to "HEX32". In this
> case,  it is not possible to control the introduced value to the set field.
>
> For example,
>
> if we introduce 0xFFFFFF7, after pressing Enter, the value changes
> automatically to 0xFFFFFF0.
> Or when 0x800007F ->  the input value changes to 0x8000080.
>
> If now,  I change the format type to "Default" again and introduce the
> value 134217855 ( 0x800007F as decimal) every works as it should.
>
> Have somebody an idea of what is happening?
>
> Kind regards,
> Pilar Gil
>
>

--
Pilar Gil Jaldo Seven Solutions | Embedded SW Engineer 2, Periodista
Rafael Gómez Montero. Edf. CETIC-UGR, Oficina 13 - Planta 1 18014,
Granada - SPAIN This e-mail and any materials attached hereto,
including, without limitation, all content hereof and thereof are
confidential and proprietary to Seven Solutions,S.L and/or its
affiliates. Without the prior written consent of Seven Solutions, this
content may not (i) be disclosed to any third party, (ii) be reproduced,
modified or otherwise used by anyone other than current employees of
Seven Solutions or its affiliates. If you are not the intended recipient
or if this message has been received in error, please immediately notify
us via e-mail and delete it.


References:
Problem when formating a field as HEX32 Pilar Gil Jaldo
Re: Problem when formating a field as HEX32 Kasemir, Kay
Re: Problem when formating a field as HEX32 Pilar Gil Jaldo

Navigate by Date:
Prev: Re: Problem when formating a field as HEX32 Pilar Gil Jaldo
Next: AKTA pure James Rezende Piton
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Problem when formating a field as HEX32 Pilar Gil Jaldo
Next: RE: Problem when formating a field as HEX32 Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024