I used a longin to get the input from the device, and used DTYP "Raw Soft Channel" and set INP to the longin. I had to add a FLNK from the record that actually did the retrieval.
Thank you,
Iain.
> -----Original Message-----
> From: Kasemir, Kay [mailto:[email protected]]
> Sent: Thursday, September 21, 2017 2:34 PM
> To: Andrew Johnson <[email protected]>; Iain Marcuson
> <[email protected]>; EPICS Tech Talk <tech-
> [email protected]>
> Subject: Re: Enumerated Strings in CSS BOY
>
> As Andrew explained, you're likely missing one level of indirection.
> Give an MBBI with
> field(ONVL, 129)
> field(ONST,"Done")
> field(THVL,1)
> field(THST,"Clearing")
>
> that record will have values 0, 1, 2, 3 represented as ?, Done, ?, Clearing
> (didn't see the detail for the ZRVL/ST and TWVL/ST for states 0 and 2)
>
>
> If you want to map raw value 1 to state 3 (ONVL=1) and raw value 129 to
> state 1 (ONVL=129), you need to get those raw values into the RVAL field.
> For example, you could have an ai record read the 1, 129, ... from your
> device, and then use INP=that record and DTYP="Raw Soft Channel" for the
> MBBI.
>
> -Kay
>
> ________________________________________
> From: [email protected] <[email protected]> on
> behalf of Andrew Johnson <[email protected]>
> Sent: Thursday, September 21, 2017 2:26 PM
> To: Iain Marcuson; EPICS Tech Talk
> Subject: Re: Enumerated Strings in CSS BOY
>
> Hi Iain,
>
> On 09/21/2017 12:45 PM, Iain Marcuson wrote:
> > My software queries a status value from a sensor. I want to display
> > the status as a string in my OPI. The status values are neither
> > sequential nor zero-indexed. I tried to create an mbbi record with
> > the *VL and *ST fields set to match the status string with the status
> > value. CSS BOY, however, does not display the string matching the
> > mbbi VAL number, but the *ST field corresponding to the VAL number. For
> example:
> >
> > Field(ONVL, 129)
> > Field(ONST,"Done")
> > Field(THVL,1)
> > Field(THST,"Clearing")
> >
> > If the mbbi VAL field is 1, then CSS BOY will display "Done" as
> > opposed to "Clearing".
> >
> > What is the preferred way of outputting a string with such an enum?
>
> The mbbi record type is designed to compare the *VL fields against the RVAL
> field, then it sets the VAL field to the index corresponding to the matching
> *VL field. The string representation of the VAL field will then be the string in
> the corresponding *ST field, and the alarm severity of the record is set from
> the corresponding *SV field.
>
> How is this record connecting to your sensor? The device support for an mbbi
> should be setting prec->rval (if you're providing your own device support). If
> this mbbi is a soft record though (i.e. DSET is unset or "Soft Channel" then
> you need to change it to be "Raw Soft Channel" - the soft support reads an
> encoded index value from the INP link directly into VAL and skips the
> comparisons with the *VL fields, whereas the raw soft support reads the INP
> link value into RVAL and goes through the *VL comparisons.
>
> HTH,
>
> - Andrew
>
> --
> Arguing for surveillance because you have nothing to hide is no different
> than making the claim, "I don't care about freedom of speech because I have
> nothing to say." -- Edward Snowdon
- References:
- Enumerated Strings in CSS BOY Iain Marcuson
- Re: Enumerated Strings in CSS BOY Andrew Johnson
- Re: Enumerated Strings in CSS BOY Kasemir, Kay
- Navigate by Date:
- Prev:
RE: new Scaler driver Mark Rivers
- Next:
PCASpy 0.7 Wang Xiaoqiang (PSI)
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Enumerated Strings in CSS BOY Kasemir, Kay
- Next:
PCASpy 0.7 Wang Xiaoqiang (PSI)
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024