1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: IOC error message on camonitor disconnect
From: Michael Davidsaver <[email protected]>
To: [email protected], [email protected]
Date: Thu, 27 Jul 2017 12:01:02 +0200
This looks like it is related to:

https://bugs.launchpad.net/epics-base/+bug/541330

Although I suspect there is more than one bug involved.


On 07/26/2017 07:58 PM, [email protected] wrote:
> Apologies, forgot to include the stack trace:
> 
>  
> 
>                 dbCore.dll!cas_commit_msg(client * pClient, unsigned int
> size) Line 357               C
> 
>                dbCore.dll!vsend_err(const caHdrLargeArray * curp, int
> status, client * client, const char * pformat, char * args) Line
> 245                C
> 
>                dbCore.dll!send_err(const caHdrLargeArray * curp, int
> status, client * client, const char * pformat, ...) Line 264  C
> 
>                dbCore.dll!camessage(client * client) Line 2571 C
> 
>                 dbCore.dll!camsgtask(void * pParm) Line 129     C
> 
>                Com.dll!epicsWin32ThreadEntry(void * lpParameter) Line
> 501    C
> 
>  
> 
> Regards,
> 
>  
> 
> Freddie
> 
>  
> 
> *From:*[email protected]
> [mailto:[email protected]] *On Behalf Of
> *[email protected]
> *Sent:* 26 July 2017 18:25
> *To:* [email protected]
> *Subject:* IOC error message on camonitor disconnect
> 
>  
> 
> Hi,
> 
>  
> 
> I am seeing this using EPICS base 3.15.5 running on windows x64. I start
> softIOC.exe and then repeatedly connect to a PV with camonitor and then
> CTRL-C the camonitor, each time I see either:
> 
>  
> 
> epics> CAS: request from 127.0.0.1:20272 => CAS: Missaligned protocol
> rejected
> 
> CAS: Request from 127.0.0.1:20272 => cmmd=26209 cid=0x150008 type=14592
> count=0 postsize=24885
> 
> CAS: Request from 127.0.0.1:20272 =>   available=0x0    N=1
> paddr=0000000000000000
> 
> CAS: forcing disconnect from 127.0.0.1:20272
> 
> epics>
> 
>  
> 
> or
> 
>  
> 
> A call to 'assert(size <= ntohs ( pMsg->m_postsize ))'
> 
>     by thread 'CAS-client' failed in ../../../src/ioc/rsrv/caserverio.c
> line 357.
> 
> Dumping a stack trace of thread 'CAS-client':
> 
> [  000007FEEE71D565]
> 
> [  000007FEEE71D206]
> 
> [  000007FEEE714EF8]
> 
> [  000007FEED1A6AD5]
> 
> [  000007FEED1AC21B]
> 
> [  000007FEED1AC29B]
> 
> [  000007FEED1AAF1C]
> 
> [  000007FEED1AAAE5]
> 
> [  000007FEEE7177F1]
> 
> [  000007FECEB3B0A8]
> 
> [  000007FECEB3AD11]
> 
> [  00000000771459CD]
> 
> [  000000007727A561]
> 
> EPICS Release EPICS R3.15.5.
> 
> Local time is 2017-07-26 16:38:50.636232257 GMT Daylight Time
> 
> Please E-mail this message to the author or to [email protected]
> <mailto:[email protected]>
> 
> Calling epicsThreadSuspendSelf()
> 
> Thread CAS-client (000000000281A040) suspended
> 
>  
> 
> It looks similar to the message reported in
> http://www.aps.anl.gov/epics/tech-talk/2016/msg01828.php
> 
>  
> 
> If I break into the program at the point of the assert I see the
> following details:
> 
>  
> 
> size = 56
> 
>  
> 
> *pMsg
> 
>    m_cmmd=256
> 
>    m_postsize=6144
> 
>    m_dataType=5120
> 
>    m_count = 256
> 
>    m_cid = 16777216
> 
>   m_available = 16777216
> 
>  
> 
> We only recently updated to 3.15.5 and I didn’t remember seeing such
> messages before, so I connected to a machine still running 3.14 and
> confirmed that I don’t get any errors reported for the same test on
> 3.14.12.6.
> 
>  
> 
> Regards,
> 
>  
> 
> Freddie
> 
>  
> 


Replies:
RE: IOC error message on camonitor disconnect freddie.akeroyd
References:
IOC error message on camonitor disconnect freddie.akeroyd
RE: IOC error message on camonitor disconnect freddie.akeroyd

Navigate by Date:
Prev: Re: Debian packages for debian 9 (stretch) ? Michael Davidsaver
Next: Re: Debian packages for debian 9 (stretch) ? Ralph Lange
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: IOC error message on camonitor disconnect freddie.akeroyd
Next: RE: IOC error message on camonitor disconnect freddie.akeroyd
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024