1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Creating an error counter
From: "Ford, Christopher" <[email protected]>
To: "Flewellen-Gore, Andrew (US)" <[email protected]>, "[email protected]" <[email protected]>
Date: Thu, 20 Jul 2017 17:52:41 +0000

Hi Andrew,

I have not seen VAL used as an operand of a calc _expression_.

Please consider setting INPB to "$(P):$(R):DEBUG:COUNTER" and then simplifying the calc _expression_ to "A+B".

Thanks,

 -Chris Ford

  SLAC



From: [email protected] <[email protected]> on behalf of Flewellen-Gore, Andrew (US) <[email protected]>
Sent: Thursday, July 20, 2017 9:49 AM
To: [email protected]
Subject: Creating an error counter
 

Hello, and thanks for reading,

 

I’m having trouble keeping a counter for the number of errors coming in from an electron microscope (SEM). I’m using the Stream device driver to listen to incoming messages from the SEM, and when a message matches a certain format that identifies it as an error message, the PV processes and stores the new error message, overwriting the last. When this happens I would like to have a second record process and increment a counter, so that I can keep track of the number of error messages coming in.

 

My current setup gets the most recent error message correctly, but does not correctly increment the counter (the counter stays at zero). Here is the relevant code from the record definition file.

 

record(waveform,$(P):$(R):DEBUG:LISTEN)  {

    field(DESC,"Holds last SEM error")

    field(DTYP,"stream")

    field(NELM,"1000")

    field(FTVL,"CHAR")

    field(SCAN,"I/O Intr")

    field(FLNK,"$(P):$(R):DEBUG:COUNTER")

    field(INP, "@devhardware.proto debugListen() L5 0")

}

 

record(calc,$(P):$(R):DEBUG:COUNTER)  {

    field(DESC,"Counter of # of errors")

    field(SCAN,"Passive")

    field(INPA,"1")

    field(CALC,"VAL+A")

}

 

When the first record processes due to an interrupt on a received error message, it is supposed to forward-link the calc record to process, causing an increment to the counter.

 

Any help or insight is appreciated.

-Andrew


Replies:
RE: Creating an error counter Mark Rivers

Navigate by Date:
Prev: Re: Creating an error counter Mooney, Tim M.
Next: RE: Creating an error counter Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Creating an error counter Ralph Lange
Next: RE: Creating an error counter Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024