1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: ioc crashing while using asyn & modbus
From: Gary Croke <[email protected]>
To: Mark Rivers <[email protected]>, Eric Norum <[email protected]>
Cc: [email protected]
Date: Wed, 12 Jul 2017 22:52:21 -0400 (EDT)
Hi Mark / Eric,

Thanks a lot for the suggestions.  First, I'll try use gdb to get the value of those pointers after the next crash.  Then I'll update to Modbus R2-9.

To answer your question Mark, I do get frequent timeouts, as there are one or two particularly 'flaky' devices.  I'm not sure if a timeout immediately precedes the crash in all cases.  I'm trying to work on the device side of things too, but I don't own the hardware.

I'll let you know the results.

Gary


----- Original Message -----
From: "Mark Rivers" <[email protected]>
To: "gcroke" <[email protected]>
Cc: [email protected]
Sent: Wednesday, July 12, 2017 9:11:11 PM
Subject: Re: ioc crashing while using asyn & modbus

Hi Gary,

I just noticed that you are using Modbus R2-8. 

R2-9 is the latest release, and this is from the R2-9 release notes.

*****************
Added error checking to make sure the length of the reply from the Modbus server is the expected value. Previously garbled communications could cause a crash because of array bounds violation.
*****************

This sounds like it could be the problem you are seeing. I suggest you try R2-9.

Mark

Sent from my iPhone

> On Jul 12, 2017, at 7:35 AM, Gary Croke <[email protected]> wrote:
> 
> Hi All,
> 
> I am using Asyn and Mark's modbus driver to talk a number of utility meters (primarily Eaton electricity meters).  My soft ioc is frequently crashing with a seg fault.  Connectivity of the meters is patchy in some cases and I cannot guarantee their availability at all times, resulting in a lot of communication errors.  In the instances I am having trouble, an intermediate gateway device hosts the modbus server and supports multiple downstream meters.  I can mitigate the situation by dedicating a soft ioc per IP address (gateway), but I'd like to identify the source of the problem if possible.  I have other iocs using the same software to talk to other models of meter without any issues.
> 
> I've tried to detail some of my configuration and the errors I'm seeing below.  Thanks for any feedback.
> 
> Gary
> 
> 
> Versions:
> =========
> EPICS:  3.14.12.3
> ASYN:   4-31
> MODBUS: 2-8
> 
> 
> Asyn & modbus driver initialization:
> ====================================
> drvAsynIPPortConfigure("pxg27", "129.57.15.27:502", 0, 1, 1)
> 
> modbusInterposeConfig("pxg27", 0, 5000)
> 
> drvModbusAsynConfigure("SA1-SB_1000", "pxg27", 1, 3, 999, 28, 8, 100, "iq150")
> drvModbusAsynConfigure("SA1-SB_1100", "pxg27", 1, 3, 1099, 18, 6, 100, "iq150")
> drvModbusAsynConfigure("SA1-SB_3118", "pxg27", 1, 3, 3117, 4, 8, 100, "iq150")
> 
> drvModbusAsynConfigure("SA2-SB_1000", "pxg27", 2, 3, 999, 28, 8, 100, "iq150")
> drvModbusAsynConfigure("SA2-SB_1100", "pxg27", 2, 3, 1099, 18, 6, 100, "iq150")
> drvModbusAsynConfigure("SA2-SB_3118", "pxg27", 2, 3, 3117, 4, 8, 100, "iq150")
> 
> ... several other asyn ports, etc. ...
> 
> dbLoadRecords("powerMetersV/db/iq150.db", "meter=SA1-SB")
> dbLoadRecords("powerMetersV/db/iq150.db", "meter=SA2-SB")
> 
> 
> Example Record:
> ===============
> record(ai,"$(meter):rcvWh") {
>    field(SCAN,"10 second")
>    field(DTYP,"asynInt32")
>    field(FLNK,"$(meter):rcvkWh")
>    field(INP,"@asyn($(meter)_1100, 0)")
>    field(EGU,"Wh")
> }
> 
> 
> Error trace #1:
> ===============
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:1807] [Compton_1000Read,0x8679f20,50] pxg12 queueUnlockPort
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:1838] [Compton_1000Read,0x8679f20,50] pxg12 asynManager::queueUnlockPort waiting for event
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:860] [pxg12,0x8660100,90] asynManager::portThread port=pxg12 callback
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:914] [pxg12,0x8660100,90] pxg12 asynManager::queueLockPortCallback signaling begin event
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:919] [pxg12,0x8660100,90] pxg12 asynManager::queueLockPortCallback waiting for mutex from queueUnlockPort
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:1841] [Compton_1000Read,0x8679f20,50] pxg12 queueUnlockPort unlock mutex 0xb4f006e0 complete.
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:1786] [HNSS_Moeller_1000Read,0x8673ee8,50] pxg12 asynManager::queueLockPort got event from callback
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/drvAsynSerial/drvAsynIPPort.c:795] [HNSS_Moeller_1000Read,0x8673ee8,50] 129.57.15.12:502 flush
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/drvAsynSerial/drvAsynIPPort.c:556] [HNSS_Moeller_1000Read,0x8673ee8,50] 129.57.15.12:502 write.
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/drvAsynSerial/drvAsynIPPort.c:558] [HNSS_Moeller_1000Read,0x8673ee8,50] 129.57.15.12:502 write 12
> 
> \000\001\000\000\000\006\002\003\003ç\000\034
> 
> 00 01 00 00 00 06 02 03 03 e7 00 1c 
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/drvAsynSerial/drvAsynIPPort.c:654] [HNSS_Moeller_1000Read,0x8673ee8,50] wrote 12 to 129.57.15.12:502, return asynSuccess.
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/interfaces/asynOctetSyncIO.c:262] [HNSS_Moeller_1000Read,0x8673ee8,50] asynOctetSyncIO wrote:
> ç
> \002\003\003ç\000\034
> 
> 02 03 03 e7 00 1c 
> 2017/07/05 15:58:06.942 [pxg12,-1,0] [../../asyn/drvAsynSerial/drvAsynIPPort.c:674] [HNSS_Moeller_1000Read,0x8673ee8,50] 129.57.15.12:502 read.
> 2017/07/05 15:58:06.942 drvModbusAsyn::doModbusIO port Compton_1000 error calling writeRead, error=129.57.15.12:502 timeout: Resource temporarily unavailable, nwrite=6/6, nread=0
> 2017/07/05 15:58:06.942 Compton:aAmps devAsynFloat64 process read error 
> 2017/07/05 15:58:06.942 Compton:abVolt devAsynFloat64 process read error 
> 2017/07/05 15:58:06.942 Compton:anVolt devAsynFloat64 process read error 
> 2017/07/05 15:58:06.942 Compton:bAmps devAsynFloat64 process read error 
> 2017/07/05 15:58:06.942 Compton:bcVolt devAsynFloat64 process read error 
> 2017/07/05 15:58:06.942 Compton:bnVolt devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:cAmps devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:caVolt devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:cnVolt devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:frequency devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:totVA devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:totVAR devAsynFloat64 process read error 
> 2017/07/05 15:58:06.943 Compton:totW devAsynFloat64 process read error 
> 2017/07/05 15:58:07.042 drvModbusAsyn::doModbusIO port Compton_1000 has I/O error
> 2017/07/05 15:58:07.042 [pxg12,-1,0] [../../asyn/asynDriver/asynManager.c:1518] [Compton_1000Read,0x8679f20,50] pxg12 addr -1 queueRequest priority 3 not lockHolder
> Segmentation fault (core dumped)
> 
> 
> Error trace #2:
> ===============
> 2017/07/11 10:03:48.585 pxg13 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:48.664 pxg12 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:48.664 drvModbusAsyn::doModbusIO port C_UPH5_3118 error calling writeRead, error=129.57.15.12:502 read error: Connection reset by peer, nwrite=6/6, nread=0
> 2017/07/11 10:03:48.664 C_UPH5:maxDemPosVAR devAsynFloat64 process read error 
> 2017/07/11 10:03:48.664 C_UPH5:maxDemPosW devAsynFloat64 process read error 
> 2017/07/11 10:03:48.686 pxg30 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:48.756 pxg11 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:48.764 drvModbusAsyn::doModbusIO port C_UPH5_3118 has I/O error
> 2017/07/11 10:03:48.780 pxg13 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:48.838 pxg11 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> ...
> 2017/07/11 10:03:52.104 pxg13 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:52.104 pxg27 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:52.104 drvModbusAsyn::doModbusIO port SA1-SB_1100 error calling writeRead, error=129.57.15.27:502 timeout: Resource temporarily unavailable, nwrite=6/6, nread=0
> 2017/07/11 10:03:52.104 SA1-SB:dlvWh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:negVARh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:netVARh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:netWh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:posVARh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:rcvWh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:totVARh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:totVAh devAsynInt32 process read error 
> 2017/07/11 10:03:52.104 SA1-SB:totWh devAsynInt32 process read error 
> 2017/07/11 10:03:52.145 pxg30 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:52.153 pxg13 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:52.189 pxg11 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:52.204 drvModbusAsyn::doModbusIO port SA1-SB_1100 has I/O error
> 2017/07/11 10:03:52.225 pxg30 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:52.278 pxg11 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> ...
> 2017/07/11 10:03:53.463 pxg13 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> 2017/07/11 10:03:53.467 pxg27 asynManager::queueLockPortCallback got mutex from queueUnlockPort, signaling end event
> Segmentation fault (core dumped)
> 
> 
> Also seen once or twice:
> ========================
> A call to 'assert(status == epicsMutexLockOK)'
>    by thread 'A/MP/HAD_9018Read' failed in ../../asyn/asynDriver/asynManager.c line 2342.
> EPICS Release EPICS R3.14.12.3 $Date: Mon 2012-12-17 14:11:47 -0600$.
> Local time is 2017-06-29 14:43:11.601380355 EDT
> Please E-mail this message to the author or to [email protected]
> Calling epicsThreadSuspendSelf()

References:
ioc crashing while using asyn & modbus Gary Croke
Re: ioc crashing while using asyn & modbus Mark Rivers

Navigate by Date:
Prev: Re: ioc crashing while using asyn & modbus Mark Rivers
Next: Re: ioc crashing while using asyn & modbus Torsten Bögershausen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: ioc crashing while using asyn & modbus Mark Rivers
Next: How to compile only for a target architecture Ricardo Herrero
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024