EPICS Home

Experimental Physics and Industrial Control System


 
1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: PVs disconnected in CSS BOY despite access through caget
From: Iain Marcuson <[email protected]>
To: "Shroff, Kunal" <[email protected]>, "[email protected] >> EPICS Tech Talk" <[email protected]>
Date: Wed, 28 Jun 2017 20:02:55 +0000

I am running 4.3.3-SNAPSHOT.  I implemented the changes you made and appear to be able to manipulate PVs.  Thank you.

 

Iain.

 

From: Shroff, Kunal [mailto:[email protected]]
Sent: Wednesday, June 28, 2017 3:04 PM
To: Iain Marcuson <[email protected]>; [email protected] >> EPICS Tech Talk <[email protected]>
Subject: RE: PVs disconnected in CSS BOY despite access through caget

 

Hi,

 

Which version of cs-studio product are you working with? You can find this information under Help -> About

 

From cs-studio 4.2 onward the configuration of the connection layer is no longer only in the PV configuration page. (We have fixed this in the newer version of cs-studio 4.4 onwards)

 

In the 4.2-4.3 versions of cs-studio, the configuration of all the ca and pva configuration are under

edit->preferences->core->diirt

 

here is an example setup for configuring default datasource and channelaccess.

https://github.com/ControlSystemStudio/org.csstudio.nsls2.product/blob/master/features/org.csstudio.nsls2.product.feature/rootfiles/diirt/datasources/datasources.xml

https://github.com/ControlSystemStudio/org.csstudio.nsls2.product/blob/master/features/org.csstudio.nsls2.product.feature/rootfiles/diirt/datasources/ca/ca.xml

 

Kunal

 

-----Original Message-----
From: [email protected] [mailto:[email protected]] On Behalf Of Iain Marcuson
Sent: Wednesday, June 28, 2017 2:57 PM
To: [email protected] >> EPICS Tech Talk <[email protected]>
Subject: PVs disconnected in CSS BOY despite access through caget

 

I am attempting to get a transferred EPICS project working.  The IOC proper seems to be working, and I can access PVs through caget.  However, when I try to access those PVs through CSS BOY, the PVs are all label "Disconnected", including the push buttons.  What might be causing this?

 

Thank you,

 

Iain.


References:
PVs disconnected in CSS BOY despite access through caget Iain Marcuson
RE: PVs disconnected in CSS BOY despite access through caget Shroff, Kunal

Navigate by Date:
Prev: RE: PVs disconnected in CSS BOY despite access through caget Shroff, Kunal
Next: Re: Area Detector and high performance NVME devices ulrik.pedersen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: PVs disconnected in CSS BOY despite access through caget Shroff, Kunal
Next: archiver quickstart 梁雅翔