1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Use case for ao record HOPR != DRVH or LOPR != DRVL?
From: "Mooney, Tim M." <[email protected]>
To: "J. Lewis Muir" <[email protected]>, EPICS Tech-Talk <[email protected]>
Date: Tue, 30 May 2017 16:58:08 +0000

You could have a device that operates in several modes with different DRV*.  If HOP* were always the same as DRV*, a display manager that didn't monitor HOP* would require the user to close and reopen the display when changing modes.


Tim Mooney ([email protected]) (630)252-5417
Beamline Controls Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab


From: [email protected] <[email protected]> on behalf of J. Lewis Muir <[email protected]>
Sent: Tuesday, May 30, 2017 11:41:38 AM
To: EPICS Tech-Talk
Subject: Use case for ao record HOPR != DRVH or LOPR != DRVL?
 
Hello, Tech-Talkers!

I understand that for the ao (Analog Output) record, the HOPR and LOPR
fields are used for the display limits and the DRVH and DRVL fields are
used for the control limits.  However, I always end up setting HOPR =
DRVH and LOPR = DRVL.  What's a use case where the display limits would
be different from the control limits (i.e., HOPR != DRVH or LOPR !=
DRVL)?

Thanks!

Lewis

References:
Use case for ao record HOPR != DRVH or LOPR != DRVL? J. Lewis Muir

Navigate by Date:
Prev: Re: Use case for ao record HOPR != DRVH or LOPR != DRVL? Pete Jemian
Next: Re: Use case for ao record HOPR != DRVH or LOPR != DRVL? Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Use case for ao record HOPR != DRVH or LOPR != DRVL? Andrew Johnson
Next: Re: Use case for ao record HOPR != DRVH or LOPR != DRVL? Ralph Lange