1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Siemens S7-300 PLC and EPICS
From: "Mueller, Joachim" <[email protected]>
To: "Florian Feldbauer" <[email protected]>, "EPICS Tech Talk" <[email protected]>
Date: Tue, 23 May 2017 13:17:29 +0200 (CEST)
Hi Florian,

here at DESY we have a couple of S7-300 and S7-1200/S7-1500 PLCs. All of 
these
are connected to EPICS via the s7plc Support from PSI. More info you can 
find at

http://epics.web.psi.ch/software/s7plc/

This works great for us, but you need to have a communications processor 
connected
to your plc. For the S7-1200 this is built in. For the S7-300 you need, for 
example, the
CP 343-1 respective the CP 1543-1 for the S7-1500.

In my opinion the s7plc is the more secure way, because you send a dedicated
number of variables to your plc. The s7nodave writes directly to the memory 
of the
plc. If I am wrong here please correct this, but I don’t like the idea that 
someone
writes into the memory of my plc ;-)

Greetings, Joachim


>-----Original Message-----
>From: [email protected] [mailto:tech-talk-
>[email protected]] On Behalf Of Florian Feldbauer
>Sent: Tuesday, May 23, 2017 11:17 AM
>To: EPICS Tech Talk
>Subject: Siemens S7-300 PLC and EPICS
>
>Hey all,
>
>for the vacuum system of our tracking detector we want to use a PLC. We
>decided to use a Siemens S7-300 which should control the pumps, gauges
>and valves of our system.
>
>The main question now is how to connect the PLC to our EPICS system?
>I've seen that the CPU module has PROFINET or PROFIBUS DP interfaces. Is
>there a device support available for those? Is there a better/easier
>interface available maybe via an additional communication processor?
>
>Any feedback appreciated!
>
>Best regards,
>
>Florian
>
>
>
>--
>----------------------------------------
>| Dr. Florian Feldbauer                |
>|                                      |
>| Ruhr-Universität Bochum              |
>| Experimentalphysik I AG              |
>| Universitätsstr 150                  |
>| D-44801 Bochum                       |
>|                                      |
>| Office: NB 2/134                     |
>| Phone:  (+49)234 / 32-23563          |
>----------------------------------------


References:
Siemens S7-300 PLC and EPICS Florian Feldbauer

Navigate by Date:
Prev: Re: Force TCP/IP reconnect from Asyn/Streamdevice Torsten Bögershausen
Next: Re: Force TCP/IP reconnect from Asyn/Streamdevice Christoph Schroeder
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Siemens S7-300 PLC and EPICS Remi FAURE
Next: support for Thorlabs ODC001 D Peter Siddons
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024