1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Disabling a record from scanning during a program event
From: Michael Davidsaver <[email protected]>
To: Iain Marcuson <[email protected]>, "[email protected] >> EPICS Tech Talk" <[email protected]>
Date: Mon, 22 May 2017 11:58:18 -0400
On 05/22/2017 11:26 AM, Iain Marcuson wrote:
> I have a setup that acquires an image from custom AreaDetector code for a custom camera.  The controller provides a command that returns the progress of an acquisition, since they can be quite long.  I have created a PV to query the progress of the acquisition, querying every 0.2 seconds.  I only want to scan when an acquisition is in progress.  I assume I would appropriately set the DISV and DISA fields of the progress PV.  However, I am lost at how I would set these variables from the acquisition code.  Is there an example or description of the bindings?

You might be able to point the SDIS link at the Acquire record.  Use the
CP link modifier.  The value read from SDIS is stored in DISA.  So
setting DISV==0 should disable the scan when Acquire==0.


Replies:
RE: Disabling a record from scanning during a program event Iain Marcuson
References:
Disabling a record from scanning during a program event Iain Marcuson

Navigate by Date:
Prev: Disabling a record from scanning during a program event Iain Marcuson
Next: RE: Disabling a record from scanning during a program event Iain Marcuson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Disabling a record from scanning during a program event Iain Marcuson
Next: RE: Disabling a record from scanning during a program event Iain Marcuson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024