1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 <2017> 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 <2017> 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Init pv properly |
From: | Miguel <[email protected]> |
To: | Andrew Johnson <[email protected]>, "Arnold, Ned D." <[email protected]>, "[email protected]" <[email protected]> |
Date: | Fri, 14 Apr 2017 18:00:17 +0100 |
On 14-04-2017 17:56, Andrew Johnson wrote:
On 04/14/2017 11:49 AM, Miguel wrote:It does work yes. Just wondering if there was a more suitable one. ThanksFor a numeric parameter that can be set by the user, the best record type to use is usually the ao record (or the longout for integers); you can then use the DRHV/DRVL fields to limit the range of values that will be accepted, and/or the IVOA field along with alarm limits to control what happens for bad values: https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Common#Invalid_Alarm_Output_Action - Andrew