On 04/14/2017 11:49 AM, Miguel wrote:
> It does work yes. Just wondering if there was a more suitable one. Thanks
For a numeric parameter that can be set by the user, the best record
type to use is usually the ao record (or the longout for integers); you
can then use the DRHV/DRVL fields to limit the range of values that will
be accepted, and/or the IVOA field along with alarm limits to control
what happens for bad values:
https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Common#Invalid_Alarm_Output_Action
- Andrew
--
Arguing for surveillance because you have nothing to hide is no
different than making the claim, "I don't care about freedom of
speech because I have nothing to say." -- Edward Snowdon
- Replies:
- Re: Init pv properly Miguel
- References:
- Init pv properly Miguel
- RE: Init pv properly Arnold, Ned D.
- Re: Init pv properly Miguel
- RE: Init pv properly Arnold, Ned D.
- Re: Init pv properly Miguel
- Navigate by Date:
- Prev:
Re: Init pv properly Miguel
- Next:
Re: Init pv properly Miguel
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Init pv properly Miguel
- Next:
Re: Init pv properly Miguel
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
|