1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 <2017> 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 <2017> 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: EPICS IOC asynMotorController error |
From: | Mark Clift <[email protected]> |
To: | "[email protected]" <[email protected]> |
Cc: | "[email protected]" <[email protected]>, "[email protected] \([email protected]\)" <[email protected]> |
Date: | Fri, 24 Mar 2017 09:02:34 +0000 |
Hi Marissa,
Regarding the limits issue, it sounds like a configuration issue.
Try changing the value of the below output record. The record only has two values 0, 1 for "Normally open switch", and "Normally closed switch". Most limit switches are normally closed
(value=1) for safety reasons.
DMC01:LIMITTYPE_CMD
DMC01:LIMITTYPE_STATUS
These records change the CN setting on the controller, check out CN in the 4080 command reference. Do an LD 0 to re-enable the limits, then test again.
Cheers,
Mark