1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Streamdevice: wild card in InTerminator?
From: Takashi OBINA <[email protected]>
To: [email protected]
Date: Fri, 17 Mar 2017 10:14:10 +0900
Hi Maren,

Please try port number 5025 instead of 5024.

Agilent LXI device uses 5024 port for interactive telnet console, and 5025 for control from a program.

Takashi Obina


On 2017/03/17 5:07, Maren Purves wrote:
Agree, is there a way of turning echo off?
(I know there was with Emulex Terminal servers :) )
How is the device connected? It may not be a setting in the
device itself but in whatever it is connected through.

Maren

On 03/16/17 04:42, Mooney, Tim M. wrote:
I'll bet that "53210A>" is a command prompt, intended to be helpful for manual operation.
You should be able to turn it off.  I'd try the SYSTem:COMMunicate:LAN:TELNet:PROMpt command.

Tim Mooney ([email protected]) (630)252-5417
Beamline Controls Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab


________________________________________
From: [email protected] [[email protected]] on behalf of Pearson, Matthew R. [[email protected]]
Sent: Thursday, March 16, 2017 8:47 AM
To: Brown, Garth
Cc: [email protected] list
Subject: Re: Streamdevice: wild card in InTerminator?

Hi,

Is there a way to modify the termination characters that the device sends back?

I’ve used an 53220A before and all it used was a ‘\n’ as it’s terminator. That was a few years ago, so firmware could have changed. But the user manual states that the SCPI terminator used is the new line character. So it’s strange that it’s sending back so much text at the end of the command.

Cheers,
Matt

Data Acquisition and Control Engineer
Spallation Neutron Source
Oak Ridge National Lab


On Mar 15, 2017, at 7:37 PM, Brown, Garth <[email protected]> wrote:

We have a 53210A frequency counter that adds "\r\n53210A> " at the end of its responses. So we specified that as the InTerminator. That worked fine until we got a 53220A. We'd like to use both of them with as little redundant code as possible. The only difference in the protocol is that 1 vs. 2 in the response. Is there a way to accommodate that small difference?
Selected lines from the protocol file:

#
InTerminator  = "\r\n53210A>";
OutTerminator = CR LF;
GET_FREQ            { out "READ?";              in "READ?\r\n%E";}

Messages from asyn related to this:
2017/03/15 16:34:21.577672 agilFC2 FCNT:AS01:1:FREQ_RBCK_RAW: Timeout after reading 39 bytes "...54132E+008<0d><0a>53220A> "
2017/03/15 16:34:22.239 diag-as01-ls02:5024 write 7
READ?\r\n
2017/03/15 16:34:22.240 diag-as01-ls02:5024 read 7
READ?\r\n
2017/03/15 16:34:22.581 diag-as01-ls02:5024 read 32
+1.18999946460060E+008\r\n53220A>
2017/03/15 16:34:27.585987 agilFC2 FCNT:AS01:1:FREQ_RBCK_RAW: Timeout after reading 39 bytes "...60060E+008<0d><0a>53220A> "

Garth









--
Takashi OBINA ([email protected])
  Phone 029-864-5200 -> 4526;  Fax: 029-864-2801

References:
Streamdevice: wild card in InTerminator? Brown, Garth
Re: Streamdevice: wild card in InTerminator? Pearson, Matthew R.
RE: Streamdevice: wild card in InTerminator? Mooney, Tim M.
Re: Streamdevice: wild card in InTerminator? Maren Purves

Navigate by Date:
Prev: Re: Streamdevice: wild card in InTerminator? Maren Purves
Next: Re: Asyn 4-30 Problem on Arm processor Jörn Dreyer
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Streamdevice: wild card in InTerminator? Maren Purves
Next: Asyn 4-30 Problem on Arm processor Jörn Dreyer
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
ANJ, 21 Dec 2017 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·