1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Command omsMAXnetConfig not found
From: Kevin Peterson <[email protected]>
To: David Vine <[email protected]>
Cc: [email protected]
Date: Fri, 3 Feb 2017 11:41:40 -0600
David,

You may run into problems caused by noise on the limit lines of the
motors controlled by the MAXnet.  I incorrectly assumed it had the same
internal filters as the MAXv.  Here is the info I received from OMS on
the subject:

  "The MAXv has a DS14C89 line driver which has internal filters.  The
MAXnet does not utilize the DS14C89 driver."

I'm still waiting for a fix from ACS to add filters to the limit lines
of their SPI-MAXnet-8000.  It is mostly unusable in its default state.

Kevin

Replies:
Re: Command omsMAXnetConfig not found David Vine
References:
Command omsMAXnetConfig not found David Vine
Re: Command omsMAXnetConfig not found Kevin Peterson
Re: Command omsMAXnetConfig not found David Vine

Navigate by Date:
Prev: Re: Command omsMAXnetConfig not found David Vine
Next: Re: Command omsMAXnetConfig not found David Vine
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Command omsMAXnetConfig not found David Vine
Next: Re: Command omsMAXnetConfig not found David Vine
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024