1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Command omsMAXnetConfig not found
From: David Vine <[email protected]>
To: Kevin Peterson <[email protected]>
Cc: [email protected]
Date: Fri, 3 Feb 2017 09:32:13 -0800
Thanks Kevin!

On Feb 3, 2017 9:29 AM, "Kevin Peterson" <[email protected]> wrote:
David,

You need to add the following lines to your stxm/stxmApp/src/Makefile in
the MOTOR section and then rebuild the IOC:

        stxm_Common_DBD += omsAsynSupport.dbd

        stxm_Common_LIBS += omsAsyn

Kevin

On 2/3/17 11:04 AM, David Vine wrote:
> Hi all,
>
> I'm trying to build an IOC to talk to a MAXnet controller using xxx-5-8
> and motor-6-9 (synApps-5-8, base-3.15.5). Nothing in
> motor-6-9/motorApp/Makefile is deselected and synApps builds without error.
>
> The st.cmd and boot output are below but the error is:
> omsMAXnetConfig("MAXNET1" , 10, "MAXNET", 10, 1000, "")
> st.cmd line 67: Command omsMAXnetConfig not found.
>
> How do I tell the IOC where to find the maxnet support?
>
> Thanks,
> David
>
>
> # MAXnet Serial
> drvAsynSerialPortConfigure("MAXNET","/dev/ttyUSB0",0,0,0)
> asynSetOption("MAXNET",0,"baud","115200")
> asynSetOption("MAXNET",0,"bits","8")
> asynSetOption("MAXNET",0,"parity","none")
> asynSetOption("MAXNET",0,"crtscts","Y")
> dbLoadRecords("$(ASYN)/db/asynRecord.db","P=oms:,R=maxnet,PORT=MAXNET,ADDR=0,OMAX=0,IMAX=0")
>
> ### Uncomment one of the following two lines:
> #asynOctetSetInputEos("MAXNET",0,"\n\r")
> asynOctetSetInputEos("MAXNET",0,"\n")
> asynOctetSetOutputEos("MAXNET",0,"\n")
>
> # omsMAXnetConfig(portName,              /* MAXnet Motor Asyn Port name */
> #                 numAxes,               /* Number of axes this
> controller supports */
> #                  serialPortName,       /* MAXnet Serial Asyn Port name */
> #                  movingPollPeriod,     /* Time to poll (msec) when an
> axis is in motion */
> #                  idlePollPeriod,       /* Time to poll (msec) when an
> axis is idle. 0 for no polling */
> #                  initString)           /* Init String sent to card */
> omsMAXnetConfig("MAXNET1" , 10, "MAXNET", 10, 1000, "")
>
>
>
> [david@dusk iocLinux]$ ../../bin/linux-x86_64/stxm st.cmd
> # Linux startup script
> # For devIocStats
> epicsEnvSet("ENGINEER","engineer")
> epicsEnvSet("LOCATION","location")
> < envPaths
> epicsEnvSet("IOC","iocLinux")
> epicsEnvSet("TOP","/opt/epics/synApps_5_8/ioc/stxm")
> epicsEnvSet("SUPPORT","/opt/epics/synApps_5_8/support")
> epicsEnvSet("EPICS_BASE","/opt/epics/base")
> epicsEnvSet("ALIVE","/opt/epics/synApps_5_8/support/alive-1-0")
> epicsEnvSet("ALLEN_BRADLEY","/opt/epics/synApps_5_8/support/allenBradley-2-3")
> epicsEnvSet("AREA_DETECTOR","/opt/epics/synApps_5_8/support/areaDetector")
> epicsEnvSet("ADCORE","/opt/epics/synApps_5_8/support/areaDetector/ADCore")
> epicsEnvSet("ADBINARIES","/opt/epics/synApps_5_8/support/areaDetector/ADBinaries")
> epicsEnvSet("ASYN","/opt/epics/synApps_5_8/support/asyn-4-30")
> epicsEnvSet("AUTOSAVE","/opt/epics/synApps_5_8/support/autosave-5-7-1")
> epicsEnvSet("BUSY","/opt/epics/synApps_5_8/support/busy-1-6-1")
> epicsEnvSet("CALC","/opt/epics/synApps_5_8/support/calc-3-4-2-1")
> epicsEnvSet("CAMAC","/opt/epics/synApps_5_8/support/camac-2-7")
> epicsEnvSet("CAPUTRECORDER","/opt/epics/synApps_5_8/support/caputRecorder-1-5-1")
> epicsEnvSet("DAC128V","/opt/epics/synApps_5_8/support/dac128V-2-8")
> epicsEnvSet("DELAYGEN","/opt/epics/synApps_5_8/support/delaygen-1-1-1")
> epicsEnvSet("DEVIOCSTATS","/opt/epics/synApps_5_8/support/devIocStats-3-1-13")
> epicsEnvSet("IP","/opt/epics/synApps_5_8/support/ip-2-17")
> epicsEnvSet("IP330","/opt/epics/synApps_5_8/support/ip330-2-8")
> epicsEnvSet("IPAC","/opt/epics/synApps_5_8/support/ipac-2-14")
> epicsEnvSet("IPUNIDIG","/opt/epics/synApps_5_8/support/ipUnidig-2-10")
> epicsEnvSet("LOVE","/opt/epics/synApps_5_8/support/love-3-2-5")
> epicsEnvSet("MCA","/opt/epics/synApps_5_8/support/mca-7-6")
> epicsEnvSet("MEASCOMP","/opt/epics/synApps_5_8/support/measComp-1-1")
> epicsEnvSet("MODBUS","/opt/epics/synApps_5_8/support/modbus-2-7")
> epicsEnvSet("MOTOR","/opt/epics/synApps_5_8/support/motor-6-9")
> epicsEnvSet("OPTICS","/opt/epics/synApps_5_8/support/optics-2-9-3")
> epicsEnvSet("SNCSEQ","/opt/epics/synApps_5_8/support/seq-2-2-3")
> epicsEnvSet("SOFTGLUE","/opt/epics/synApps_5_8/support/softGlue-2-4-3")
> epicsEnvSet("SSCAN","/opt/epics/synApps_5_8/support/sscan-2-10")
> epicsEnvSet("STD","/opt/epics/synApps_5_8/support/std-3-4")
> epicsEnvSet("STREAM","/opt/epics/synApps_5_8/support/stream-2-6a")
> epicsEnvSet("VAC","/opt/epics/synApps_5_8/support/vac-1-5-1")
> epicsEnvSet("VME","/opt/epics/synApps_5_8/support/vme-2-8-2")
> epicsEnvSet("XXX","/opt/epics/synApps_5_8/support/xxx-5-8")
> # save_restore.cmd needs the full path to the startup directory, which
> # envPaths currently does not provide
> epicsEnvSet(STARTUP,/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux)
> # Increase size of buffer for error logging from default 1256
> errlogInit(20000)
> # Specify largest array CA will transport
> # Note for N doubles, need N*8 bytes+some overhead
> epicsEnvSet EPICS_CA_MAX_ARRAY_BYTES 64010
> epicsEnvSet ("STREAM_PROTOCOL_PATH", ".:../protocols")
> ################################################################################
> # Tell EPICS all about the record types, device-support modules, drivers,
> # etc. in the software we just loaded (stxm.munch)
> dbLoadDatabase("../../dbd/iocstxmLinux.dbd")
> iocstxmLinux_registerRecordDeviceDriver(pdbbase)
> ### save_restore setup
> < save_restore.cmd
> # BEGIN save_restore.cmd
> ------------------------------------------------------
> ### save_restore setup
> # status PVs
> #save_restoreSet_UseStatusPVs(1)
> save_restoreSet_status_prefix("stxm:")
> dbLoadRecords("/opt/epics/synApps_5_8/support/autosave-5-7-1/asApp/Db/save_restoreStatus.db",
> "P=stxm:, DEAD_SECONDS=5")
> # Ok to save/restore save sets with missing values (no CA connection to PV)?
> save_restoreSet_IncompleteSetsOk(1)
> # Save dated backup files?
> save_restoreSet_DatedBackupFiles(1)
> # Number of sequenced backup files to write
> save_restoreSet_NumSeqFiles(3)
> # Time interval between sequenced backups
> save_restoreSet_SeqPeriodInSeconds(300)
> # Ok to retry connecting to PVs whose initial connection attempt failed?
> save_restoreSet_CAReconnect(1)
> # Time interval in seconds between forced save-file writes.  (-1 means
> forever).
> # This is intended to get save files written even if the normal trigger
> mechanism is broken.
> save_restoreSet_CallbackTimeout(-1)
> # specify where save files should be
> set_savefile_path("/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux",
> "autosave")
> ###
> # specify what save files should be restored.  Note these files must be
> # in the directory specified in set_savefile_path(), or, if that function
> # has not been called, from the directory current when iocInit is invoked
> set_pass0_restoreFile("auto_positions.sav", "P=stxm:")
> # Save positions every five seconds
> doAfterIocInit("create_monitor_set('auto_positions.req',5,'P=stxm:')")
> set_pass0_restoreFile("auto_settings.sav", "P=stxm:")
> set_pass1_restoreFile("auto_settings.sav", "P=stxm:")
> # save settings every thirty seconds
> doAfterIocInit("create_monitor_set('auto_settings.req',30,'P=stxm:')")
> # Note that you can reload these sets after creating them: e.g.,
> # reload_monitor_set("auto_settings.req",30,"P=stxm:")
> # Note that you can restore a .sav file without also autosaving to it.
> #set_pass0_restoreFile("myInitData.sav")
> #set_pass1_restoreFile("myInitData.sav")
> # Also, you can restore a .sav file that contains macros. (autosave R5-4-2)
> #set_pass0_restoreFile("myGenericData.sav", "P=stxm:")
> #set_pass1_restoreFile("myGenericData.sav", "P=stxm:")
> ###
> # specify directories in which to to search for included request files
> set_requestfile_path("/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux", "")
> set_requestfile_path("/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux",
> "autosave")
> set_requestfile_path("/opt/epics/synApps_5_8/support/areaDetector",
> "ADApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/areaDetector/ADCore",
> "ADApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/autosave-5-7-1",
> "asApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/busy-1-6-1",
> "busyApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/calc-3-4-2-1",
> "calcApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/camac-2-7",
> "camacApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/caputRecorder-1-5-1",
> "caputRecorderApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/dac128V-2-8",
> "dac128VApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/delaygen-1-1-1",
> "delaygenApp/Db")
> macLib: macro DXP is undefined (expanding string
> set_requestfile_path("$(DXP)", "dxpApp/Db"))
> set_requestfile_path("/opt/epics/synApps_5_8/support/ip-2-17", "ipApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/ip330-2-8",
> "ip330App/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/ipUnidig-2-10",
> "ipUnidigApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/love-3-2-5",
> "loveApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/mca-7-6", "mcaApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/measComp-1-1",
> "measCompApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/modbus-2-7",
> "modbusApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/motor-6-9",
> "motorApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/optics-2-9-3",
> "opticsApp/Db")
> macLib: macro QUADEM is undefined (expanding string
> set_requestfile_path("$(QUADEM)", "quadEMApp/Db"))
> set_requestfile_path("/opt/epics/synApps_5_8/support/sscan-2-10",
> "sscanApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/softGlue-2-4-3",
> "softGlueApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/std-3-4", "stdApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/vac-1-5-1",
> "vacApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/support/vme-2-8-2",
> "vmeApp/Db")
> set_requestfile_path("/opt/epics/synApps_5_8/ioc/stxm", "stxmApp/Db")
> # Debug-output level
> save_restoreSet_Debug(0)
> # Tell autosave to automatically build built_settings.req and
> # built_positions.req from databases and macros supplied to dbLoadRecords()
> # (and dbLoadTemplate(), which calls dbLoadRecords()).
> epicsEnvSet("BUILT_SETTINGS", "built_settings.req")
> epicsEnvSet("BUILT_POSITIONS", "built_positions.req")
> autosaveBuild("built_settings.req", "_settings.req", 1)
> pretending to register a dbLoadRecords hook
> autosaveBuild("built_positions.req", "_positions.req", 1)
> # END save_restore.cmd
> --------------------------------------------------------
> # Access Security
> dbLoadRecords("/opt/epics/synApps_5_8/ioc/stxm/stxmApp/Db/Security_Control.db","P=stxm:")
> asSetFilename("/opt/epics/synApps_5_8/ioc/stxm/iocBoot/accessSecurity.acf")
> asSetSubstitutions("P=stxm:")
> # soft scaler for testing
> < softScaler.cmd
> # soft scaler
> dbLoadRecords("/opt/epics/synApps_5_8/support/asyn-4-30/db/asynRecord.db","P=stxm:,R=asynScaler,PORT=scaler1Port,ADDR=0,OMAX=0,IMAX=0")
> # drvScalerSoftConfigure(char *portName, int maxChans, char *pvTemplate)
> drvScalerSoftConfigure("scaler1Port", 8, "stxm:scaler1:s%d")
> dbLoadRecords("/opt/epics/synApps_5_8/support/std-3-4/stdApp/Db/scaler.db","P=stxm:,S=scaler1,OUT=@asyn(scaler1Port
> 0 0),DTYP=Asyn Scaler,FREQ=10000000")
> dbLoadRecords("/opt/epics/synApps_5_8/support/std-3-4/stdApp/Db/scalerSoftCtrl.db","P=stxm:,Q=scaler1:,SCALER=stxm:scaler1")
> # user-assignable ramp/tweak
> dbLoadRecords("/opt/epics/synApps_5_8/support/std-3-4/stdApp/Db/ramp_tweak.db","P=stxm:,Q=rt1")
> ### Motors
> dbLoadTemplate("motor.substitutions.MAXnet")
> dbLoadTemplate: error opening sub file motor.substitutions.MAXnet
> #dbLoadTemplate("MAXnetAux.substitutions")
> # MAXnet IP
> #drvAsynIPPortConfigure("MAXNET","maxnet-ip-address:23",0,0,0)
> # MAXnet Serial
> drvAsynSerialPortConfigure("MAXNET","/dev/ttyUSB0",0,0,0)
> asynSetOption("MAXNET",0,"baud","115200")
> asynSetOption("MAXNET",0,"bits","8")
> asynSetOption("MAXNET",0,"parity","none")
> asynSetOption("MAXNET",0,"crtscts","Y")
> dbLoadRecords("/opt/epics/synApps_5_8/support/asyn-4-30/db/asynRecord.db","P=oms:,R=maxnet,PORT=MAXNET,ADDR=0,OMAX=0,IMAX=0")
> ### Uncomment one of the following two lines:
> #asynOctetSetInputEos("MAXNET",0,"\n\r")
> asynOctetSetInputEos("MAXNET",0,"\n")
> asynOctetSetOutputEos("MAXNET",0,"\n")
> # omsMAXnetConfig(portName,              /* MAXnet Motor Asyn Port name */
> #                 numAxes,               /* Number of axes this
> controller supports */
> #                  serialPortName,       /* MAXnet Serial Asyn Port name */
> #                  movingPollPeriod,     /* Time to poll (msec) when an
> axis is in motion */
> #                  idlePollPeriod,       /* Time to poll (msec) when an
> axis is idle. 0 for no polling */
> #                  initString)           /* Init String sent to card */
> omsMAXnetConfig("MAXNET1" , 10, "MAXNET", 10, 1000, "")
> st.cmd line 67: Command omsMAXnetConfig not found.
> ### Scan-support software
> # crate-resident scan.  This executes 1D, 2D, 3D, and 4D scans, and caches
> # 1D data, but it doesn't store anything to disk.  (See 'saveData' below
> for that.)
> dbLoadRecords("/opt/epics/synApps_5_8/support/sscan-2-10/sscanApp/Db/standardScans.db","P=stxm:,MAXPTS1=1000,MAXPTS2=1000,MAXPTS3=1000,MAXPTS4=1000,MAXPTSH=1000")
> dbLoadRecords("/opt/epics/synApps_5_8/support/sscan-2-10/sscanApp/Db/saveData.db","P=stxm:")
> # Run this after iocInit:
> doAfterIocInit("saveData_Init(saveData.req, 'P=stxm:')")
> dbLoadRecords("/opt/epics/synApps_5_8/support/sscan-2-10/sscanApp/Db/scanProgress.db","P=stxm:scanProgress:")
> # Run this after iocInit:
> doAfterIocInit("seq &scanProgress, 'S=stxm:, P=stxm:scanProgress:'")
> # configMenu example.
> dbLoadRecords("/opt/epics/synApps_5_8/support/autosave-5-7-1/asApp/Db/configMenu.db","P=stxm:,CONFIG=scan1")
> # Note that the request file MUST be named $(CONFIG)Menu.req
> # If the macro CONFIGMENU is defined with any value, backup (".savB") and
> # sequence files (".savN") will not be written.  We don't want these for
> configMenu.
> # Run this after iocInit:
> doAfterIocInit("create_manual_set('scan1Menu.req','P=stxm:,CONFIG=scan1,CONFIGMENU=1')")
> # You could make scan configurations read-only:
> #dbLoadRecords("$(AUTOSAVE)/asApp/Db/configMenu.db","P=stxm:,CONFIG=scan1,ENABLE_SAVE=0")
> # read-only configMenu example.  (Read-only, because we're not calling
> create_manual_set().)
> #dbLoadRecords("$(AUTOSAVE)/asApp/Db/configMenu.db","P=stxm:,CONFIG=scan2")
> # A set of scan parameters for each positioner.  This is a convenience
> # for the user.  It can contain an entry for each scannable thing in the
> # crate.
> dbLoadTemplate("scanParms.substitutions")
> ### Stuff for user programming ###
> < calc.cmd
> ### Stuff for user programming ###
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userCalcs10.db","P=stxm:")
> appendToFile("built_settings.req", '$(P)userCalcEnable')
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userCalcOuts10.db","P=stxm:")
> appendToFile("built_settings.req", '$(P)userCalcOutEnable')
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userCalcOuts10more.db","P=stxm:,N1=11,N2=12,N3=13,N4=14,N5=15,N6=16,N7=17,N8=18,N9=19,N10=20")
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userStringCalcs10.db","P=stxm:")
> appendToFile("built_settings.req", '$(P)userStringCalcEnable')
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userArrayCalcs10.db","P=stxm:,N=8000")
> appendToFile("built_settings.req", '$(P)userArrayCalcEnable')
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userTransforms10.db","P=stxm:")
> appendToFile("built_settings.req", '$(P)userTranEnable')
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userAve10.db","P=stxm:")
> # string sequence (sseq) records
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/userStringSeqs10.db","P=stxm:")
> appendToFile("built_settings.req", '$(P)userStringSeqEnable')
> # editSseq - edit any sseq or seq record
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/editSseq.db",
> "P=stxm:,Q=ES:")
> doAfterIocInit("seq &editSseq, 'P=stxm:,Q=ES:'")
> # interpolation
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/interp.db",
> "P=stxm:,N=2000")
> dbLoadRecords("/opt/epics/synApps_5_8/support/calc-3-4-2-1/calcApp/Db/interpNew.db",
> "P=stxm:,Q=1,N=2000")
> # pvHistory (in-crate archive of up to three PV's)
> dbLoadRecords("/opt/epics/synApps_5_8/support/std-3-4/stdApp/Db/pvHistory.db","P=stxm:,N=1,MAXSAMPLES=1440")
> # busy record
> dbLoadRecords("/opt/epics/synApps_5_8/support/busy-1-6-1/busyApp/Db/busyRecord.db",
> "P=stxm:,R=mybusy")
> dbLoadRecords("/opt/epics/synApps_5_8/support/busy-1-6-1/busyApp/Db/busyRecord.db",
> "P=stxm:,R=mybusy2")
> # Soft function generator
> #dbLoadRecords("$(CALC)/calcApp/Db/FuncGen.db","P=stxm:,Q=fgen,OUT=stxm:m7.VAL")
> # Slow feedback
> dbLoadTemplate "pid_slow.substitutions"
> dbLoadTemplate "async_pid_slow.substitutions"
> #dbLoadTemplate "fb_epid.substitutions"
> # Miscellaneous PV's, such as burtResult
> dbLoadRecords("/opt/epics/synApps_5_8/support/std-3-4/stdApp/Db/misc.db","P=stxm:")
> # devIocStats
> dbLoadRecords("/opt/epics/synApps_5_8/support/devIocStats-3-1-13/db/iocAdminSoft.db","IOC=stxm")
> ### Load database record for alive heartbeating support.
> # RHOST specifies the IP address that receives the heartbeats.
> #dbLoadRecords("$(ALIVE)/aliveApp/Db/alive.db", "P=stxm:,RHOST=X.X.X.X")
> ###############################################################################
> iocInit
> Starting iocInit
> ############################################################################
> ## EPICS R3.15.5
> ## EPICS Base built Jan 26 2017
> ############################################################################
> reboot_restore: entry for file 'auto_positions.sav'
> reboot_restore: Found filename 'auto_positions.sav' in restoreFileList.
> *** restoring from
> '/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux/autosave/auto_positions.sav'
> at initHookState 6 (before record/device init) ***
> reboot_restore: done with file 'auto_positions.sav'
>
> reboot_restore: entry for file 'auto_settings.sav'
> reboot_restore: Found filename 'auto_settings.sav' in restoreFileList.
> *** restoring from
> '/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux/autosave/auto_settings.sav'
> at initHookState 6 (before record/device init) ***
> reboot_restore: done with file 'auto_settings.sav'
>
> recDynLinkOut: waiting for CA context
> reboot_restore: entry for file 'auto_settings.sav'
> reboot_restore: Found filename 'auto_settings.sav' in restoreFileList.
> *** restoring from
> '/opt/epics/synApps_5_8/ioc/stxm/iocBoot/iocLinux/autosave/auto_settings.sav'
> at initHookState 7 (after record/device init) ***
> reboot_restore: done with file 'auto_settings.sav'
>
> recDynLinkOut: got CA context
> iocRun: All initialization complete
> create_monitor_set('auto_positions.req',5,'P=stxm:')
> create_monitor_set('auto_settings.req',30,'P=stxm:')
> auto_positions.sav: 0 of 0 PV's connected
> saveData_Init(saveData.req, 'P=stxm:')
> saveData: message queue created
> saveData:maxAllowedRetries = 10
> saveData:retryWaitInSecs = 15
> seq &scanProgress, 'S=stxm:, P=stxm:scanProgress:'
> sevr=info Sequencer release 2.2.3, compiled Thu Jan 26 13:28:16 2017
> sevr=info Spawning sequencer program "scanProgress", thread 0x249e420:
> "scanProgress"
> sevr=info scanProgress[0]: all channels connected & received 1st monitor
> create_manual_set('scan1Menu.req','P=stxm:,CONFIG=scan1,CONFIGMENU=1')
> seq &editSseq, 'P=stxm:,Q=ES:'
> sevr=info Sequencer release 2.2.3, compiled Thu Jan 26 13:28:16 2017
> sevr=info Spawning sequencer program "editSseq", thread 0x24b6610:
> "editSseq"
> sevr=info editSseq[0]: all channels connected & received 1st monitor
> sevr=minor ca_array_get_callback( typeToCA(type), count, var->chid,
> pvCaGetHandler, arg): Virtual circuit disconnect
> ###############################################################################
> # write all the PV names to a local file
> dbl > dbl-all.txt
> # Report  states of database CA links
> dbcar(*,1)
> CA links in all records
>
>                stxm:pid_slow.INP  --> stxm:IP330_1                  (0, 0)
>                stxm:pid_slow.OUTL --> stxm:DAC3_1                   (0, 0)
>           stxm:pid_slowStop2.OUT  --> stxm:DAC3_1                   (0, 0)
>  stxm:pid_slowOUT_tweak_down.INPB --> stxm:DAC3_1                   (0, 0)
>  stxm:pid_slowOUT_tweak_down.OUT  --> stxm:DAC3_1                   (0, 0)
>    stxm:pid_slowOUT_tweak_up.INPB --> stxm:DAC3_1                   (0, 0)
>    stxm:pid_slowOUT_tweak_up.OUT  --> stxm:DAC3_1                   (0, 0)
>       stxm:history1_PV1_DESC.DOL  --> .DESC                         (0, 0)
>       stxm:history1_PV2_DESC.DOL  --> .DESC                         (0, 0)
>       stxm:history1_PV3_DESC.DOL  --> .DESC                         (0, 0)
>
> Total 270 CA links; 260 connected, 10 not connected.
>     0 can't read, 0 can't write.  (0 disconnects, 0 writes prohibited)
>
> # print the time our boot was finished
> date
> 2017/02/03 08:57:44.475244
> epics> scan1Menu.sav: 365 of 365 PV's connected
> auto_settings.sav: 6 of 6 PV's connected
>
>
>
>


Replies:
Re: Command omsMAXnetConfig not found Kevin Peterson
References:
Command omsMAXnetConfig not found David Vine
Re: Command omsMAXnetConfig not found Kevin Peterson

Navigate by Date:
Prev: Re: Command omsMAXnetConfig not found Kevin Peterson
Next: Re: Command omsMAXnetConfig not found Kevin Peterson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Command omsMAXnetConfig not found Kevin Peterson
Next: Re: Command omsMAXnetConfig not found Kevin Peterson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024