EPICS Home

Experimental Physics and Industrial Control System


 
1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: BACnet driver writing values to a device
From: Kyle Lanclos <[email protected]>
To: "Webb, Steven B." <[email protected]>
Cc: "[email protected]" <[email protected]>
Date: Tue, 3 Jan 2017 15:10:39 -1000
Steven B. <[email protected]> wrote:
> It looks like you are missing the “Priority” parameter in the OUT-field.

That was a key component of what I was missing. I was also missing the
need to separate out input and output as distinct channels for proper
read/write access.

Thanks again for the pointer.

--Kyle