The OS is Linux, RHEL 6.
I think problem could be on ioc, I will check this,
Regards
Em 03-01-2017 11:11, Mark Rivers escreveu:
Those dbScan warnings are very unusual. It makes me think there is something wrong with the timer system, because, for example the 0.5 second scan thread appears to be running much faster than 0.5 seconds, since it is averaging 0.00 seconds. What operating system is this?
Mark
________________________________________
From: [email protected] [[email protected]] on behalf of Gabriel de Souza Fedel [[email protected]]
Sent: Tuesday, January 03, 2017 5:57 AM
To: [email protected]
Subject: Default value to field SCAN
Hi,
When I create records and don't set the field SCAN, what is the default
value? There is an way to change this?
I'm having problems with a set of records without SCAN field that are
consuming a lot of CPU, and receiving this messages:
dbScan warning from '.2 second' scan thread:
Scan processing averages 0,00 seconds (0,00 .. 0,02).
Over-runs have now happened 283681 times in a row.
To fix this, move some records to a slower scan rate.
dbScan warning from '.5 second' scan thread:
Scan processing averages 0,00 seconds (0,00 .. 0,03).
Over-runs have now happened 290049 times in a row.
To fix this, move some records to a slower scan rate.
dbScan warning from '.1 second' scan thread:
Scan processing averages 0,00 seconds (0,00 .. 0,03).
Over-runs have now happened 278431 times in a row.
To fix this, move some records to a slower scan rate.
If i remove small choices from dbd file (.1, .2 and .5 seconds) solves
the problem. Apparently the records are being created with all SCAN
values...some idea to solve this?
Regards,
--
Gabriel Fedel
Software de Operação das Linhas de Luz
Laboratório Nacional de Luz Síncrotron – (LNLS)
Centro Nacional de Pesquisa em Energia e Materiais (CNPEM)
[email protected] | +55 (19) 3512 1226
www.lnls.cnpem.br
--
Gabriel Fedel
Software de Operação das Linhas de Luz
Laboratório Nacional de Luz Síncrotron – (LNLS)
Centro Nacional de Pesquisa em Energia e Materiais (CNPEM)
[email protected] | +55 (19) 3512 1226
www.lnls.cnpem.br
- References:
- Default value to field SCAN Gabriel de Souza Fedel
- RE: Default value to field SCAN Mark Rivers
- Navigate by Date:
- Prev:
RE: Default value to field SCAN Mark Rivers
- Next:
RE: Asyn support Heesterman, Peter J
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: Default value to field SCAN Mark Rivers
- Next:
Re: Default value to field SCAN Andrew Johnson
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
|