1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: CA connection problems between VxWorks and Windows
From: Benjamin Franksen <[email protected]>
To: EPICS Techtalk <[email protected]>
Date: Fri, 5 Aug 2016 17:23:07 +0200
I (re-)send this problem description by a colleague of mine with the
hope that perhaps someone has encountered similar problems and/or has an
idea how to further debug this.

"""
We have a PC with Windows 7 that has Labview and an EPICS base 3.14.12.2
installed. This PC connects to several channel access servers. The
servers that are Linux based, like a channel access gateway and a
softioc, make no problems. However, since last week, connections to a
vxWorks IOC are no longer possible.

"cainfo" for a PV on this IOC replies something like "connection reset
by host", although the correct host is mentioned. So it seems that the
name resolution request for the PV works but the connection to actually
transmit the data is interrupted or can't be established at all. Both
systems are within the same network collision domain.

A Linux channel access client in the same network has no problems with
it's connections to the same PVs, so it doesn't seem to be a server
related problem.

Now, if we change the IP address on the windows PC to another free
address in the network, channel access first works. Everything is fine
but only for 3 to 5 minutes. Then connections to the vxWorks IOC fail
again. Setting the IP address to a third variant has the same effect.
Everything works but only for a few minutes. Setting the IP address back
to the original one still doesn't work. Deactivating and  re-activating
the network interface doesn't help. After a while, maybe  15 to 30
minutes, an IP address that didn't work and wasn't used for that time,
can be used again, but still, only for 2 to 3 minutes.

Setting EPICS_CA_ADDR_LIST to the IP of the IOC and
EPICS_CA_AUTO_ADDR_LIST to "no" doesn't help. But channel access on the
windows PC is not completely broken. Requesting PVs from our linux
based channel access gateway or a linux soft-IOC always works.
"""

Cheers
Ben

Attachment: signature.asc
Description: OpenPGP digital signature


Replies:
Re: CA connection problems between VxWorks and Windows Michael Davidsaver
Re: CA connection problems between VxWorks and Windows Benjamin Franksen

Navigate by Date:
Prev: RE: CARS:Modbus - function 06 (write single register) issue Nick Levchenko
Next: Re: CA connection problems between VxWorks and Windows Michael Davidsaver
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Paramveer Jain
Next: Re: CA connection problems between VxWorks and Windows Michael Davidsaver
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Oct 2016 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·