EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Serial port COM10: not work?
From: Eric Norum <[email protected]>
To: "Heesterman, Peter J" <[email protected]>
Cc: "EPICS Tech-Talk \([email protected]\)" <[email protected]>
Date: Tue, 29 Sep 2015 11:14:53 -0700
There may be a limit in the operating system, but not in the ASYN serial port driver (you are talking about ASYN, right?).  There’s no check at all on the serial port name -- the drvAsynSerialPortConfigure serial line name argument is passed directly to the ‘open’ system call.

On Sep 29, 2015, at 11:04 AM, Heesterman, Peter J <[email protected]> wrote:

The devices (pump controllers) are named TT01, TT02, TT03, TT04, NT07 and NT10, respectively.
These were attached to COM1, COM2, COM3, COM4, COM7 and COM10 (only in the interests of matching the number scheme, above).
 
When I installed the software, the first five worked perfectly.
But the last one was unable to connect.
 
On a hunch, we re-mapped the last comport to COM8:, in the operating system.
Now all 6 work perfectly.
 
I wondered if there is a single-numeric-digit constraint, on the serial port number?

-- 
Eric Norum
[email protected]





Replies:
RE: Serial port COM10: not work? freddie.akeroyd
References:
Serial port COM10: not work? Heesterman, Peter J

Navigate by Date:
Prev: Serial port COM10: not work? Heesterman, Peter J
Next: RE: Serial port COM10: not work? freddie.akeroyd
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Serial port COM10: not work? Heesterman, Peter J
Next: RE: Serial port COM10: not work? freddie.akeroyd
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 16 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·