EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Asyn ModbusTCP communication KO without error messages
From: haquin <[email protected]>
To: tech-talk <[email protected]>
Date: Wed, 2 Sep 2015 16:00:10 +0200
Hi all,

I have a VxWorks IOC (with MVME-CPU using both eth interfaces) communicating with a siemens S7PLC via Asyn/ModbusTCP.
EPICS release 3.14.12.4 Asyn v4.22

After a while (1 or 2 days), the communication is not working anymore ... but I have no error messages (no timeout nor disconnection ...).
From IOC side I a have "Read Multiple Register" function reading the whole modbus table (109 registers) every second
and a "Write Multiple Register" function writing the value of a counter incremented every seconds from record level.

When I activate AsynTrace on IP Port or Read or Write ports there is no messages ...
asynReport on Read port indicates only 1 Read OK
asynReport on Write port indicates 0 Write OK

I can read the PLC register via "modpoll" tool from a Linux PC
I can start a Linux IOC connected to the same PLC
The netstat command on IOC shell tells that the TCP port is established but the Recv-Q is not equal to 0 (12 for example)

What can explain this behavior ?

thanks in advance !

--
Christophe Haquin
Control and Real Time systems Engineer

+33 231454661 office
+33 231454728 fax
SdA/GIM
GANIL
Bd Henri Becquerel BP 55027
14076 CAEN CEDEX5

begin:vcard
fn:Christophe Haquin
n:Haquin;Christophe
email;internet:[email protected]
tel;work:02 31 45 46 61
x-mozilla-html:FALSE
version:2.1
end:vcard


Replies:
RE: Asyn ModbusTCP communication KO without error messages Mark Rivers

Navigate by Date:
Prev: Re: Virtual Circuit Disconnect Warning Andrew Johnson
Next: RE: Asyn ModbusTCP communication KO without error messages Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Custom SQL data source for CSS Petro Kazmirchuk
Next: RE: Asyn ModbusTCP communication KO without error messages Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 16 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·