1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: MEDM issues
From: Mark Rivers <[email protected]>
To: "'D Peter Siddons'" <[email protected]>, "[email protected]" <[email protected]>
Date: Mon, 16 Mar 2015 15:30:31 +0000
I just tested with your example adl file.  

I was able to change the bar orientation from "right" to "up" in Edit mode with no problem.

When I attempt to set  PV Limits/Precision/LOPR/HOPR/PREC to "User specified" in Edit mode it simply reverts to Channel.

When I set PV Limits/LOPR/HOPR/PREC to "User specified" in Execute mode it works fine, I can change the display limits and precision.

I don't get a seg fault in any of these cases.

Medm 3.1.9, base 3.14.12.4.

Mark


-----Original Message-----
From: [email protected] [mailto:[email protected]] On Behalf Of D Peter Siddons
Sent: Monday, March 16, 2015 10:15 AM
To: [email protected]
Subject: Re: MEDM issues

Hi Mark,
    Not sure :) The Debian packages installed are libmotif-dev 2.3.4.6 
and friends.
Pete.


On 03/15/2015 01:33 PM, Mark Rivers wrote:
> Hi Pete,
>
> I just tested medm 3.1.9 on Fedora 15 and I did not have problems.  You are setting the display precision of User Specified when in edit or run mode?  I don't think you can change it in edit mode, only at runtime.
>
> What motif package are you using?  I believe I am using lesstif-devel-0.95.2-2.fc15.x86_64.
>
> Mark
>
> ________________________________________
> From: [email protected] [[email protected]] on behalf of D Peter Siddons [[email protected]]
> Sent: Sunday, March 15, 2015 10:42 AM
> To: [email protected]
> Subject: MEDM issues
>
> Hi,
> I've attached a medm screen. I'm having problems with the Bar Monitor
> widget.
>
> In edit mode:
>
> Setting direction to "up" gives:
> *** stack smashing detected ***: medm terminated
>
> Setting display precision to User Specified gives:
> SIGSEGV
>
> [1]+  Aborted                 (core dumped) medm scintscal.adl
>
> This is with medm-3.1.9 and epics base-3.14.12.4 on Ubuntu 14.10.
>
> Anyone else having problems?
>
> Pete.
>
>
> --
> D. Peter Siddons
> Detector Development Group Leader
> Bldg. 535B
> Photon Sciences Directorate,
> Brookhaven National Laboratory
> Upton, NY 11973
>
> email: [email protected]
> Phone: (631) 344-2738
>
>

-- 
D. Peter Siddons
Detector Development Group Leader
Bldg. 535B
Photon Sciences Directorate,
Brookhaven National Laboratory
Upton, NY 11973

email: [email protected]
Phone: (631) 344-2738



References:
MEDM issues D Peter Siddons
RE: MEDM issues Mark Rivers
Re: MEDM issues D Peter Siddons

Navigate by Date:
Prev: Re: MEDM issues D Peter Siddons
Next: RE: Asyn record proccessing( read functions) during PINI=YES Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: MEDM issues D Peter Siddons
Next: Re: MEDM issues Paul Sichta
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 16 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·