1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: How to handle out-of-index of MBBO/MBBI?
From: Jeong Han Lee <[email protected]>
To: [email protected]
Date: Thu, 05 Mar 2015 08:48:37 +0900
Once I add only the IVOA field into mbbo as

field(IVOA, "Don't drive outputs")

The case 2) error wasn't printed out in the IOC console anymore. The UNSV field doesn't show any difference so far. I will investigate them later.

By the way, in the EPICS wiki, https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Common, I see three possible selections in Invalid Alarm Output Action section are CONTINUE, NO_OUTPUT, and OUTPUT_IVOV.
IOC returns the following message:

Can't set "ECR11-Diag:FC01:SetADRate.IVOA" to "NO_OUTPUT"
Error at or before ")" in file "db/devkeithley6514.db" line 522

However, Michael and Chris told me to use "Don't drive outputs" and I found three possible selections such as "Continue normally", "Don't drive outputs", and "Set output to IVOV" in menuIvoa.dbd. No error messages I can see in the IOC. I guess the wiki is out-of-date. Am I correct?

Thank you, Michael and Chris!

Thanks,
Han



On 03/04/2015 11:13 PM, Michael Davidsaver wrote:
On 03/04/2015 12:12 AM, Jeong Han Lee wrote:
...
   Here is my question:

   How to ignore out-of-range index in mbbo or mbbi in both cases?
   Where I have to implement it?

You should to investigate the UNSV and IVOA fields of mbboRecord.  The
combination of UNSV=INVALID and IVOA="Don't drive outputs" might be
closer to what you want.


--
Jeong Han Lee, Dr.rer.nat.
---------------------------
Accelerator Systems Division
Rare Isotope Science Project
Institute for Basic Science
Daejeon, South Korea
---------------------------
tel  : +82-42-878-8733
fax  : +82-42-878-8799

Replies:
Re: How to handle out-of-index of MBBO/MBBI? Andrew Johnson
References:
How to handle out-of-index of MBBO/MBBI? Jeong Han Lee
Re: How to handle out-of-index of MBBO/MBBI? Michael Davidsaver

Navigate by Date:
Prev: Re: error on the IOC shell for asyn driver Rod Nussbaumer
Next: RE: Problem with HDF5 plugin for areaDetector Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: How to handle out-of-index of MBBO/MBBI? Michael Davidsaver
Next: Re: How to handle out-of-index of MBBO/MBBI? Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 16 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·