1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Support for hivolt power supply
From: Jörn Wüstenfeld <[email protected]>
To: [email protected]
Date: Thu, 16 Oct 2014 07:23:17 +0200
Dear Emma,

these are ISEG power supplys. Depending on the interface type (USB, Serial or 
CAN bus), you need different methodes to access them. For the USB interface, 
you just need an protocol file for the streamdev suppoprt of the asyn driver, 
for the serial interface you need to use an asynPortDriver, due to the very 
slow speed of the interface. For the CAN bus you need a special interface from 
PEAK, as the ISEG CAN bus devices are hard to get working with other CAN 
interfaces.
For the USB or the serial interface I can send you my code which supports the 
full functionality. Note that these devices do not have internal ramping, so 
this has to be done via sequenzers on the IOC side, if needed, which I do not 
have yet.

Regards,
Jörn

Am Mittwoch, 15. Oktober 2014, 22:09:56 schrieb Emma Shepherd:
> Hi all,
> 
> We need to develop EPICS support for a hivolt.de T1CP power supply.  So here
> comes the usual question - has anybody by any chance already done this?
> 
> Cheers,
> Emma

Attachment: smime.p7s
Description: S/MIME cryptographic signature


References:
Support for hivolt power supply Emma Shepherd

Navigate by Date:
Prev: Re: EPICS on vxWorks Andrew Johnson
Next: Re: areadetector, iocSimDetector can not be started on OS X due to dyld: Symbol not found: _xmlFree Heinz Junkes
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Support for hivolt power supply Emma Shepherd
Next: Usage of the dbNameToAddr funciton ZHANG Zhaohong
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 17 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·