1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Recommended Control HWs for High Voltage Platform
From: Heinz Junkes <[email protected]>
To: Jeong Han Lee <[email protected]>
Cc: EPICS tech-talk <[email protected]>
Date: Mon, 4 Aug 2014 12:31:39 +0000
Han,

we run a similiar system here at the FHI FEL.
It is our HV Gun Control.

IOC is running on a debian-VM connected to the ethernet.
Using asynDrv and StreamDevice2

A Moxa  NPort 6450 (4 Ports) on "ground-level" 

3 Power supplies (floated to HV) are connected to the Moxa serial ports via Moxa Fibre-Connectors (TCF-90)

1.) Agilent E3634A as current source
2.) Delta as Voltage Source (200V)
3.) Sorensen as Voltage Source (80 - 120V)


2 Spellman HV-Powersupplies (SL-Model, 50kV and 20 kV). These devices are equipped with an Digital Interface (SIC) which provides
ethernet (we are using) and RS-232 on ground level.

Best regards,
Heinz

------------------------------------------------------------------------------
Fritz-Haber-Institut    | Phone:         (+49 30) 8413-4270
Heinz Junkes             | Fax (G3+G4):   (+49 30) 8413-5900
Faradayweg 4-6        | 
D - 14195 Berlin        | E-Mail:        [email protected]
------------------------------------------------------------------------------

On 31.07.2014, at 12:24, Jeong Han Lee <[email protected]> wrote:

> Dear All,
> 
>  We are designing a control system, which is, of course, based on EPICS, for ECR Ion Source. There are three electrical potentials present in our configuration. The first one is definitely the ground, the second is at 45kV, and the other is at 75kV above the ground.
> 
>  All devices and equipment, HV controller, vacuum, and so on, which we want to monitor, are located at each HV potential.
> 
>  A naive thought, which I have right now, is that MOXA NPort 56XX, Ethernet Switch with Fiber Optic links, and EPICS IOC running on Linux Platform should be enough.
> 
>  Do you have any example which I can follow within EPICS collaboration?
> 
>  Any suggestions and recommendation about HWs, designs, and others are welcome always.
> 
>  Thanks,
>  Han
> 
> 
> 
> -- 
> Jeong Han Lee, Dr.rer.nat.
> ----------------------------
> Accelerator Systems Division
> Rare Isotope Science Project
> Institute for Basic Science
> Daejeon, South Korea
> ----------------------------
> tel  : +82-42-878-8733
> fax  : +82-42-878-8799

Attachment: smime.p7s
Description: S/MIME cryptographic signature


Replies:
Re: Recommended Control HWs for High Voltage Platform Jeong Han Lee
References:
Recommended Control HWs for High Voltage Platform Jeong Han Lee

Navigate by Date:
Prev: RE: 回复: RE: 回复:epicsqt on arm board Andrew Rhyder
Next: Re: Recommended Control HWs for High Voltage Platform Jeong Han Lee
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Recommended Control HWs for High Voltage Platform Jeong Han Lee
Next: Re: Recommended Control HWs for High Voltage Platform Jeong Han Lee
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  <20142015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 17 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·