1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: All Pvs disconnected
From: Julio Calvo <[email protected]>
To: Mark Rivers <[email protected]>, techtalkForo <[email protected]>
Date: Thu, 28 Nov 2013 16:31:52 +0000 (GMT)
I have changed that variables but still not working.
 
I have the same configuration of that machine, here, and it works, without internet. And it is not connected, no cable.
 
Thanks.
 
Julio.


El Jueves 28 de noviembre de 2013 17:01, Mark Rivers <[email protected]> escribió:
If the Ethernet port is disconnected then CA does not work.  I think if you set EPICS_CA_AUTO_ADDR_LIST=NO and EPICS_CA_ADDR_LIST=localhost it will work, but I am not certain.

You could also just plug the Ethernet cable into a cheap switch with nothing else connected to it :-)

Mark

________________________________

From: [email protected] [[email protected]] on behalf of Julio Calvo [[email protected]]
Sent: Thursday, November 28, 2013 9:53 AM
To: techtalkForo
Subject: All Pvs disconnected

Hello,

I have move a computer from my lab, it was working perfectly, it was connected to internet, now, this computer is in other place without internet connection for security reasons. I have open the IOC, pvs are ok after dbl. But CSS GUI appears as disconnected, any idea?. I have done this several times and I never found this problem. Do I have to configure something?.

Thanks.

Julio.



Replies:
RE: All Pvs disconnected Mark Rivers
References:
All Pvs disconnected Julio Calvo
RE: All Pvs disconnected Mark Rivers

Navigate by Date:
Prev: RE: All Pvs disconnected Mark Rivers
Next: RE: All Pvs disconnected Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: All Pvs disconnected Mark Rivers
Next: RE: All Pvs disconnected Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 20 Apr 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·