On 11/19/13 11:15 AM, Benoit wrote:
> Hi,
>
> I would like to use mV in my EPICS folder and send V to my driver. I
> have done conversion correctly using asynInt32 type but it doesn't
> work with asynFloat64. Do you have any suggestion?
Hi, Benoit.
Remove the PINI, LINR, and ESLO fields from CavVoltSet. Add a calcout
record named CavMillivoltSet to convert to V and write the value
via its OUT field to CavVoltSet. Set the PINI field to "YES" on
CavMillivoltSet.
Lewis