1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Error while opening OPI
From: "Kasemir, Kay" <[email protected]>
To: Swati Soni2 <[email protected]>
Cc: "[email protected]" <[email protected]>
Date: Mon, 11 Nov 2013 08:35:07 -0500
On Nov 11, 2013, at 1:08 AM, Swati Soni2 <[email protected]<mailto:[email protected]>> wrote:
I am beginner of EPICS...I had created one OPI file but on opening it is showing the error : Premature end of file

Can anyone tell me how to resolve this issue???
This may be a result of how you create the *.opi file.

If you run CS-Studio, then use File/New, and select "OPI File" from the "BOY" category, this will create a very basic *.opi XML file and open it in the BOY editor.
If you opened that same file in a text editor, you would see that it follows the format

<display typeId="org.csstudio.opibuilder.Display" version="1.0.0">
</display>

On the other hand, if you use other means to create a file that's simply named *.opi, for example via File/New, the use "File" from the "General" category, and name it "test.opi", you will get that error "Failed to open opi file, premature end of file".
That's because this second file is totally empty, it doesn't have any of the expected *.opi file content.

-Kay




References:
Error while opening OPI Swati Soni2

Navigate by Date:
Prev: Re: Subscription updates halting? Dirk Zimoch
Next: RE: autosave failure S_rpcLib_RPC_CANTSEND Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Error while opening OPI Swati Soni2
Next: PV access over the Network. Ganesh Jangir
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 20 Apr 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·