1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: LabVIEW EPICS Communication on ports other than 5064? [SEC=UNCLASSIFIED:For-Official-Use-Only]
From: Carsten Winkler <[email protected]>
To: "BUTTON, David" <[email protected]>, "[email protected]" <[email protected]>
Date: Wed, 6 Nov 2013 09:05:35 +0100
Hello Dave,

please set the environment variable EPICS_CA_SERVER_PORT for all systems with running CA Lab clients and they will connect.
You're right, CA Lab runs only on Windows and Linux PCs but not on real-time controllers.
God luck with the EPICS IO Server.

Regards,
Carsten

Am 06.11.2013 08:26, schrieb BUTTON, David:

Hello,

Locally our EPICS control system has been modified so that the several IOC servers which are running of the computer we call control have had their EPICS_CA_SERVER_PORT variable set to values other than 5064, ie 49200 and 49212...  Needles to say that both the EPICS IO Server native to LabVIEW is now unable to access the PV's, and likewise the CALab vi's can no longer access them either.  I am unable to discover if there is a way to change the "port number" so that I can get either the NI or CALabs vi's working again. The native I/O server is important as it runs on the real-time controllers where I believe the CA Lab vi’s can only run on a windows application.  I am only recently started down this path of LabVIEW EPICS communications, and would greatly appreciate input.

Thanks in advance,

Dave





Helmholtz-Zentrum Berlin für Materialien und Energie GmbH

Mitglied der Hermann von Helmholtz-Gemeinschaft Deutscher Forschungszentren e.V.

Aufsichtsrat: Vorsitzender Prof. Dr. Dr. h.c. mult. Joachim Treusch, stv. Vorsitzende Dr. Beatrix Vierkorn-Rudolph
Geschäftsführung: Prof. Dr. Anke Rita Kaysser-Pyzalla, Thomas Frederking

Sitz Berlin, AG Charlottenburg, 89 HRB 5583

Postadresse:
Hahn-Meitner-Platz 1
D-14109 Berlin

http://www.helmholtz-berlin.de

References:
LabVIEW EPICS Communication on ports other than 5064? [SEC=UNCLASSIFIED:For-Official-Use-Only] BUTTON, David

Navigate by Date:
Prev: LabVIEW EPICS Communication on ports other than 5064? [SEC=UNCLASSIFIED:For-Official-Use-Only] BUTTON, David
Next: RE: LabVIEW EPICS Communication on ports other than 5064? [SEC=UNOFFICIAL] BUTTON, David
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: LabVIEW EPICS Communication on ports other than 5064? [SEC=UNCLASSIFIED:For-Official-Use-Only] BUTTON, David
Next: Re: LabVIEW EPICS Communication on ports other than 5064? [SEC=UNCLASSIFIED:For-Official-Use-Only] Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024