Hi Florian,
In general I would recommend using pasynUser->reason for the "parameter number" and using the addr parameter for the "motor number". That is more in the spirit of how they are intended to be used, and allows your driver to work with the next version of your motor controller which might support multiple axes.
Your db file would then look like:
record(ao, "$(P)$(R)Velocity) {
field(DTYP, "asynInt32")
field(OUT, "($(PORT),$(ADDR))VELOCITY")
}
ADDR is the motor number (0 for the current controller) and VELOCITY is the asynDrvUser parameter.
Your driver would implement the asynDrvUser interface to convert the string "VELOCITY" into the appropriate "parameter number", which it places in pasynUser->reason.
Mark
________________________________________
From: [email protected] [[email protected]] on behalf of Florian Feldbauer [[email protected]]
Sent: Friday, February 15, 2013 3:14 AM
To: EPICS Tech Talk
Subject: AsynInt32 device support and mbbo records
Hey,
I have written an AsynPortDriver for the TMCM142 1 axis stepper
driver/controller
The motor driver is connected via CAN bus and expects a message with 7
bytes of data:
byte 0: command number
byte 1: parameter number (I'm using the addr parameter from the asyn
interface)
byte 2: motor number (only one motor can be connected to the driver so
it is always 0)
byte 3-6: data (32 bit signed int)
For setting the microstep resolution of the motor driver the data has to
be a number between
0 and 11, each coding a different resoultion.
I wanted to use a mbbo record, which looks like this:
record( mbbo, "PANDA:$(subsys):MOTOR:$(SECTOR):SAP:USTEPRESOLUTION" ) {
field( DTYP, "asynUInt32" )
field( OUT, "@asyn($(BUS),27,1)TMCM142_SAP" )
field( ZRST, "2048 micro steps" )
field( ONST, "1024 micro steps" )
field( TWST, "512 micro steps" )
field( THST, "256 micro steps" )
field( FRST, "128 micro steps" )
field( FVST, "64 micro steps" )
field( SXST, "32 micro steps" )
field( SVST, "16 micro steps" )
field( EIST, "8 micro steps" )
field( NIST, "4 micro steps" )
field( TEST, "2 micro steps" )
field( ELST, "1 micro steps" )
}
Unfortunately, the value inside my writeInt32 function from the
asynPortDriver is always 0.
Do I have to set the ZRVL,...,ELVL fields for asynInt32? Or do I need
another asyn interface for
this record?
Best regards,
Florian
--
----------------------------------------
| Dr. Florian Feldbauer |
| |
| Helmholtz-Institut Mainz / |
| Johannes Gutenberg-Universität Mainz |
| Johann-Joachim-Becher-Weg 45 |
| D-55128 Mainz |
| |
| Office: 01/217 |
| Phone: (+49)6131 / 39-25829 |
----------------------------------------
- Replies:
- Re: AsynInt32 device support and mbbo records Florian Feldbauer
- References:
- AsynInt32 device support and mbbo records Florian Feldbauer
- Navigate by Date:
- Prev:
New version of LabVIEW-EPICS-interface CA Lab 1.4.1.0 Carsten Winkler
- Next:
Re: AsynInt32 device support and mbbo records Florian Feldbauer
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: AsynInt32 device support and mbbo records Hu, Yong
- Next:
Re: AsynInt32 device support and mbbo records Florian Feldbauer
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|