1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Analog data acquisition in an EMI environment
From: Paul Sichta <[email protected]>
To: Pavel Maslov <[email protected]>
Cc: EPICS Tech Talk <[email protected]>
Date: Thu, 31 Jan 2013 08:48:00 -0500
Pavel,
Once we have the isolated +/- 10 volt  signal from the CTD (two for
redundancy) we connect to a signal conditioner and finally to ADC's .
Our power supply controls and protection systems are not EPICS, but
real-time Linux  (redHawk from Concurrent). We use the LKCO to measure
magnet current for NSTX, our fusion device.

To measure high voltage, we have used the resistor-divider technique
you mention (special HV resistors) to get a measurement down to 10
volt range for conventional ADC.

We also use PPPL-designed  point-point fiber optic links for analog
signals (ADC - serial/digital on fiber - DAC).

-ps


On Thu, Jan 31, 2013 at 1:48 AM, Pavel Maslov <[email protected]> wrote:
> Hi Paul,
>
> Thanks for the information. We'll check the LKCO out, it might be a good
> alternative to the NXCT.
> But I am more interested in how you have embedded it in your control system.
> Or is it just hooked to the oscilloscope so you catch a single pulse? Just
> out of curiosity, what kind of experiments do you perform with this sensor?
>
> Any ideas on the voltage transducer? How do you measure high-voltage at
> Princeton?
>
>
>
> --
> Best regards,
>
>
> Pavel Maslov, MS
> Controls Engineer at Pulsed power Lab
> Efremov Institute for Electro-Physical Apparatus
> St. Petersburg, Russia
>
> Mobile: +7 (951) 672 22 19
> Landline: +7 (812) 461 01 01

Replies:
Re: Analog data acquisition in an EMI environment Pavel Maslov
References:
Analog data acquisition in an EMI environment Pavel Maslov
Re: Analog data acquisition in an EMI environment Paul Sichta
Re: Analog data acquisition in an EMI environment Pavel Maslov

Navigate by Date:
Prev: Re: Analog data acquisition in an EMI environment Pavel Maslov
Next: Java, CAJ, DNS RE: CSS addr_list bug Kasemir, Kay
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Analog data acquisition in an EMI environment Pavel Maslov
Next: Re: Analog data acquisition in an EMI environment Pavel Maslov
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024