1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: .PACT .TIME
From: Rok Šabjan <[email protected]>
To: Pavel Maslov <[email protected]>
Cc: EPICS Tech Talk <[email protected]>
Date: Wed, 12 Dec 2012 15:43:48 +0100
Pavel,

maybe you could make use of the timestamp record. It will update it's value if it is linked to your record. That you can display on the screen.

Rok


On 12. dec. 2012, at 15:35, Pavel Maslov wrote:

Leo, 

I need an operator (the client) to see if the record has been processed. Your advice works on the IOC side only.


On Wed, Dec 12, 2012 at 5:54 PM, Dalesio, Leo <[email protected]> wrote:

Login and set the TPRO field to a non zero value.

It will print the name of the record and every passive record processed in this lock set after the record with the TPRO field set to 1.

 

Or, set the deadband of an AI or CALC to -1. It will post the VAL field each time as the absolute value of the change will exceed it.

 

 

From: [email protected] [mailto:[email protected]] On Behalf Of Pavel Maslov
Sent: Wednesday, December 12, 2012 8:39 AM
To: EPICS Tech Talk
Subject: .PACT .TIME

 

Hi, 

 

Is there a way I can subscribe to these record fields?

I would like to know if my record has been processed.

The record itself is being processed ~30 seconds.

 

It's strange when I caget record.PACT I can see 1 or 0. However, camonitor doesn't react on the value change whatsoever.

 

Is there any other way around?


 

--
Best regards,


Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia

Mobile: +7 (951) 672 22 19
Landline: +7 (812) 461 01 01




--
Best regards,


Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia

Mobile: +7 (951) 672 22 19
Landline: +7 (812) 461 01 01



References:
.PACT .TIME Pavel Maslov
Re: .PACT .TIME Pavel Maslov

Navigate by Date:
Prev: RE: .PACT .TIME Dalesio, Leo
Next: RE: .PACT .TIME matthew.pearson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: .PACT .TIME Pavel Maslov
Next: RE: .PACT .TIME matthew.pearson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024