1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Data acquisition for ICP accelerometers
From: Mark Rivers <[email protected]>
To: Matt Rippa <[email protected]>, "[email protected]" <[email protected]>
Date: Wed, 28 Nov 2012 02:57:23 +0000
Hi Matt,

The APS is building an EPICS system to monitor floor vibration using the USB devices from Measurement Computing. Here are links to a few models:

http://www.mccdaq.com/usb-data-acquisition/USB-1608FS-Plus.aspx

http://www.mccdaq.com/usb-data-acquisition/USB-1608G-Series.aspx

They are in the range of $400 to $800 for 8 to 16-channels, 16-bit.

They accept an external trigger so you can synchronize multiple units.

My EPICS software for the Measurement Computing modules is here:

http://cars9.uchicago.edu/software/epics/measCompDoc.html

Bad news: My driver is Windows-only
Good news: They do have a Linux SDK
Bad news: The Linux SDK is written in C#, so it needs the "mono" compiler, and I don't think it can be used from C or C++ EPICS code.
Good news: The Linux SDK is itself open-source, so it could be re-written in C++.

Cheers,
Mark


________________________________________
From: [email protected] [[email protected]] on behalf of Matt Rippa [[email protected]]
Sent: Tuesday, November 27, 2012 8:39 PM
To: [email protected]
Subject: Data acquisition for ICP accelerometers

Hi,

Has anyone worked with vibration monitoring and analysis in
EPICS? We're looking for a digitizing system with 24 or more
channels and dynamic range of 96 dB or higher. Our sensors are
ICP accelerometers with resolution down to 50 ug's (uV) and
sensitivity of 1V/g.

It seems there are plenty of 'turn-key' systems out there with
Windows only. For example, this is a good fit but no linux/epics.

http://www.spectraldynamics.com/index.php/products/puma

Thanks,
-Matt



References:
Data acquisition for ICP accelerometers Matt Rippa

Navigate by Date:
Prev: Data acquisition for ICP accelerometers Matt Rippa
Next: Re: posix osiSpawnDetachedProcess inherits scheduling policy + priority Till Straumann
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Data acquisition for ICP accelerometers Matt Rippa
Next: RE: Data acquisition for ICP accelerometers matthew.pearson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·