1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: streamDevice 32-bit hex value read problem
From: Dirk Zimoch <[email protected]>
To: "Martin L. Smith" <[email protected]>
Cc: [email protected]
Date: Tue, 13 Nov 2012 09:49:40 +0100
Hi Marty,

%R is the floating point raw format. The integer raw format is %r.

(Here I assume that you really get binary data, not the hex string "ffffffff ffffffff", which would be a case for %x.)

I am a bit confused, because ffffffff ffffffff is 2 32 bit values or 1 64 bit value.

Stream device can read a 32 bit big endian signed integer with %4r, a 32 bit big endian unsigned integer with %04r, a 32 bit little endian signed integer with %#4r and so on.

On 64 bit machines, StreamDevice can even read 64 bit integers with %8r, but no EPICS record can store them. So you are limited to 32 bit signed or unsigned at the moment.

In case you do not have binary data but hex strings, (and the space in your format suggests that) you should use %x.

Dirk


On 12.11.2012 21:21, Martin L. Smith wrote:
I'm trying to read a 32-bit hex value like ffffffff ffffffff using
EPICS R3.14.12.2, streamDevice 2-5, and asyn 4-19 on 64-bit Linux OS.

When I read these values using the following protocol:
get_ilock {
out "din";
in "%(\$1FirstInterlockWord.VAL)8R ",
"%(\$1SecondInterlockWord.VAL)0R";

ExtraInput = Ignore;
}

Both records are longin records and no matter if I use the 8R or 0R I
always get the same result:

ID06ds:FirstInterlockWord 11/12/12 14:03:02.743812335 -2147483648
ID06ds:SecondInterlockWord 11/12/12 14:03:02.743823268 -2147483648

Turns out that this is hex value 80000000

If I use a strngin record I can see that I'm getting the expected data.

Is this the largest value that I can read using streamDevice or is there
some other way that I should try to read these values?

Thanks,
Marty



Replies:
Re: streamDevice 32-bit hex value read problem Martin L. Smith
References:
streamDevice 32-bit hex value read problem Martin L. Smith

Navigate by Date:
Prev: question of Hytec 8516 added in synApps-5.3 李芳
Next: Re: question of Hytec 8516 added in synApps-5.3 Paul Hamadyk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: streamDevice 32-bit hex value read problem Allison, Stephanie
Next: Re: streamDevice 32-bit hex value read problem Martin L. Smith
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·