1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: calc VAL field not updating from bi VAL field
From: Tim Mooney <[email protected]>
To: "J. Lewis Muir" <[email protected]>
Cc: EPICS Tech Talk <[email protected]>
Date: Wed, 30 May 2012 14:21:43 -0500 (CDT)
Lewis,
This is just bizarre.  I don't see this problem on a roughly comparable VME system.  I'm stumped and flailing.
Two things that I haven't seen proof of so far are that the calc record actually is processing, and that the "=" operator works.
Could you set 17lab:ClcBacklightBi.TPRO to 1, and also try "a<>1?0:1".
Could you try a calcout record, so you can check the CLCV field?
Tim

----- Original Message -----
From: "J. Lewis Muir" <[email protected]>
To: "EPICS Tech Talk" <[email protected]>
Sent: Tuesday, May 29, 2012 10:09:53 PM
Subject: calc VAL field not updating from bi VAL field

I've got a problem where a calc record's VAL field is not
updating when I expect it to.

I load the following database into my IOC:

calc-bi.db >>>
record(bi, "$(P)Unidig1Bi1") {
  field(ZNAM, "Low")
  field(ONAM, "High")
}

record(calc, "$(P)ClcBacklightBi") {
  field(INPA, "$(P)Unidig1Bi1.VAL CP MS")
  field(CALC, "A=1?1:0")
}
<<<

like this:

st.cmd >>>
...
dbLoadRecords("calc-bi.db","P=17lab:")
...
<<<

I then start camonitor:

camonitor console >>>
$ camonitor 17lab:ClcBacklightBi.VAL 17lab:ClcBacklightBi.A
17lab:ClcBacklightBi.VAL       2012-05-29 19:48:44.845452 1 LINK
INVALID
17lab:ClcBacklightBi.A         2012-05-29 19:48:44.845452 0 LINK
INVALID
<<<

And then I perform a series of caput commands in another console:

caput console >>>
$ caput 17lab:Unidig1Bi1.VAL 0
Old : 17lab:Unidig1Bi1.VAL           Low
New : 17lab:Unidig1Bi1.VAL           Low
$ caput 17lab:Unidig1Bi1.VAL 1
Old : 17lab:Unidig1Bi1.VAL           Low
New : 17lab:Unidig1Bi1.VAL           High
$ caput 17lab:Unidig1Bi1.VAL 0
Old : 17lab:Unidig1Bi1.VAL           High
New : 17lab:Unidig1Bi1.VAL           Low
$ caput 17lab:Unidig1Bi1.VAL 1
Old : 17lab:Unidig1Bi1.VAL           Low
New : 17lab:Unidig1Bi1.VAL           High
<<<

camonitor shows the following:

camonitor console >>>
17lab:ClcBacklightBi.VAL       2012-05-29 21:11:28.307312 1
17lab:ClcBacklightBi.A         2012-05-29 21:11:28.307312 0
17lab:ClcBacklightBi.A         2012-05-29 21:11:33.423978 1
17lab:ClcBacklightBi.A         2012-05-29 21:11:36.990645 0
17lab:ClcBacklightBi.A         2012-05-29 21:12:32.507352 1
<<<

As you can see, the 17lab:ClcBacklightBi record's VAL field
updates once when the record first processes and then never
again.  The "A" field is updating correctly as I change
17lab:Unidig1Bi1.VAL, but 17lab:ClcBacklightBi.VAL never updates
again.

If I change the CALC expression to "A", the VAL field updates
correctly.  If I change it back, it stops working again.

Environment:
* VME processor module: Motorola MVME-2100 (vxWorks-ppc603)
  - CPU: MPC 8240
  - Memory: 32 MB
* OS: VxWorks 5.5.2
* Kernel: WIND 2.6
* BSP: mv2100-asd5 (by Andrew Johnson)
* Build toolchain: Tornado 2.2.2
* EPICS 3.14.12.2 (+Known Problems patches)

I tried this on darwin-x86 (x86_64) and it did not fail, so to
date it is only failing for me on my VME systems.  (I initially
discovered the problem on an MVME-5100.)

This worked fine with older software (i.e. VxWorks 5.4.2 with
EPICS 3.14.11) on my VME systems.

Thanks,

Lewis

-- 
Tim Mooney ([email protected]) (630)252-5417
Software Services Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab

Replies:
Re: calc VAL field not updating from bi VAL field Tim Mooney
Re: calc VAL field not updating from bi VAL field J. Lewis Muir
RE: calc VAL field not updating from bi VAL field Mark Rivers
References:
calc VAL field not updating from bi VAL field J. Lewis Muir

Navigate by Date:
Prev: Re: Proposed change in asyn - request for comments Eric Norum
Next: Re: calc VAL field not updating from bi VAL field Tim Mooney
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: calc VAL field not updating from bi VAL field J. Lewis Muir
Next: Re: calc VAL field not updating from bi VAL field Tim Mooney
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024