1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: calc VAL field not updating from bi VAL field
From: "Allison, Stephanie" <[email protected]>
To: "J. Lewis Muir" <[email protected]>, EPICS Tech Talk <[email protected]>
Date: Wed, 30 May 2012 08:55:46 -0700
Hi Lewis -

Could this be a round-off error (long to double)?  Does this CALC work:

field(CALC, "A>0.5?1:0")

Stephanie

> -----Original Message-----
> From: [email protected] [mailto:[email protected]] On Behalf
> Of J. Lewis Muir
> Sent: Tuesday, May 29, 2012 8:10 PM
> To: EPICS Tech Talk
> Subject: calc VAL field not updating from bi VAL field
> 
> I've got a problem where a calc record's VAL field is not
> updating when I expect it to.
> 
> I load the following database into my IOC:
> 
> calc-bi.db >>>
> record(bi, "$(P)Unidig1Bi1") {
>   field(ZNAM, "Low")
>   field(ONAM, "High")
> }
> 
> record(calc, "$(P)ClcBacklightBi") {
>   field(INPA, "$(P)Unidig1Bi1.VAL CP MS")
>   field(CALC, "A=1?1:0")
> }
> <<<
> 
> like this:
> 
> st.cmd >>>
> ...
> dbLoadRecords("calc-bi.db","P=17lab:")
> ...
> <<<
> 
> I then start camonitor:
> 
> camonitor console >>>
> $ camonitor 17lab:ClcBacklightBi.VAL 17lab:ClcBacklightBi.A
> 17lab:ClcBacklightBi.VAL       2012-05-29 19:48:44.845452 1 LINK
> INVALID
> 17lab:ClcBacklightBi.A         2012-05-29 19:48:44.845452 0 LINK
> INVALID
> <<<
> 
> And then I perform a series of caput commands in another console:
> 
> caput console >>>
> $ caput 17lab:Unidig1Bi1.VAL 0
> Old : 17lab:Unidig1Bi1.VAL           Low
> New : 17lab:Unidig1Bi1.VAL           Low
> $ caput 17lab:Unidig1Bi1.VAL 1
> Old : 17lab:Unidig1Bi1.VAL           Low
> New : 17lab:Unidig1Bi1.VAL           High
> $ caput 17lab:Unidig1Bi1.VAL 0
> Old : 17lab:Unidig1Bi1.VAL           High
> New : 17lab:Unidig1Bi1.VAL           Low
> $ caput 17lab:Unidig1Bi1.VAL 1
> Old : 17lab:Unidig1Bi1.VAL           Low
> New : 17lab:Unidig1Bi1.VAL           High
> <<<
> 
> camonitor shows the following:
> 
> camonitor console >>>
> 17lab:ClcBacklightBi.VAL       2012-05-29 21:11:28.307312 1
> 17lab:ClcBacklightBi.A         2012-05-29 21:11:28.307312 0
> 17lab:ClcBacklightBi.A         2012-05-29 21:11:33.423978 1
> 17lab:ClcBacklightBi.A         2012-05-29 21:11:36.990645 0
> 17lab:ClcBacklightBi.A         2012-05-29 21:12:32.507352 1
> <<<
> 
> As you can see, the 17lab:ClcBacklightBi record's VAL field
> updates once when the record first processes and then never
> again.  The "A" field is updating correctly as I change
> 17lab:Unidig1Bi1.VAL, but 17lab:ClcBacklightBi.VAL never updates
> again.
> 
> If I change the CALC expression to "A", the VAL field updates
> correctly.  If I change it back, it stops working again.
> 
> Environment:
> * VME processor module: Motorola MVME-2100 (vxWorks-ppc603)
>   - CPU: MPC 8240
>   - Memory: 32 MB
> * OS: VxWorks 5.5.2
> * Kernel: WIND 2.6
> * BSP: mv2100-asd5 (by Andrew Johnson)
> * Build toolchain: Tornado 2.2.2
> * EPICS 3.14.12.2 (+Known Problems patches)
> 
> I tried this on darwin-x86 (x86_64) and it did not fail, so to
> date it is only failing for me on my VME systems.  (I initially
> discovered the problem on an MVME-5100.)
> 
> This worked fine with older software (i.e. VxWorks 5.4.2 with
> EPICS 3.14.11) on my VME systems.
> 
> Thanks,
> 
> Lewis


Replies:
Re: calc VAL field not updating from bi VAL field Andrew Johnson
Re: calc VAL field not updating from bi VAL field J. Lewis Muir
References:
calc VAL field not updating from bi VAL field J. Lewis Muir

Navigate by Date:
Prev: Re: Proposed change in asyn - request for comments Eric Norum
Next: Re: Proposed change in asyn - request for comments Michael Davidsaver
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: calc VAL field not updating from bi VAL field J. Lewis Muir
Next: Re: calc VAL field not updating from bi VAL field Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·