1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: About "dbCaMonitorLink" ?
From: <[email protected]>
To: "Mark Rivers" <[email protected]>
Cc: EPICS tech-talk <[email protected]>
Date: Wed, 28 Mar 2012 10:48:22 +0900
Dear Mark;

Thanks a lot for your quick response!

I should have been more careful in reading the manual before
posting the question.

Thank you again.

Best regards,

J. Odagiri


----- Original Message -----
> I think you can just do:
> 
> record(ai, "pressure_in_torr")
> {
>     field(DTYP, "Soft Channel")
>     field(INP, "loek_current CP MS")
> }
> 
> CP means process this record whenever a channel access monitor is 
received on the INP link PV.
> 
> Mark
> 
> 
> ________________________________________
> From: [email protected] [[email protected]] on 
behalf of [email protected] [[email protected]]
> Sent: Tuesday, March 27, 2012 7:59 PM
> To: EPICS tech-talk
> Subject: About "dbCaMonitorLink" ?
> 
> Dear All;
> 
> I have a question on dbCaLink.
> 
> Suppose an IOC has a PV like this:
> 
> record(ai, "pressure_in_torr")
> {
>     field(DTYP, "Soft Channel")
>     field(INP, "loek_current")
> 
>       ...
> 
> }
> 
> and another IOC has the referred PV something like this:
> 
> record(ai, "leak_current")
> {
>     field(SCAN, ".1 second")
>     field(DTYP, "SOME_DEVICS")
>     field(INP, "@some:address")
> 
>      ...
> 
> }
> 
> In this situation, the referring PV, "pressure_in_torr",
> also needs to be scanned periodically to get the value
> from "leak_current" through dbCaGetLink.
> 
> I'm wondering if I could use monitor function of CA to
> transfer the data between the two IOCs so as not to cause
> unnecessary traffic on the network. As far as I know,
> there is no function something like "dbCaMonitorLink".
> 
> Is there any way to realize what I want to do?
> I appreciate any comments and suggestions.
> 
> Thanks a lot in advance.
> 
> Jun-ichi Odagiri (KEK)
> 
> 
> 
> 
> 
> 
> 


References:
About "dbCaMonitorLink" ? jun-ichi.odagiri
RE: About "dbCaMonitorLink" ? Mark Rivers

Navigate by Date:
Prev: RE: About "dbCaMonitorLink" ? Mark Rivers
Next: Re: Build problem with db dependencies Bruce Hill
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: About "dbCaMonitorLink" ? Mark Rivers
Next: Extract a column of data from 2D Waveform Record Peter Milne
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·