Mark,
Thanks for such a quick response! Yeah, I forgot to include that dbd. I have recompiled and here what I've got:
drvAsynIPPortConfigure("L0", "172.20.92.3", 0, 0, 0)
drvAsynIPPortConfigure: "172.20.92.3" is not of the form "<host>:<port> [protocol]"
Port L0 connectDevice failed: asynManager:connectDevice port L0 not found
asynOctetSetOutputEos("L0",0,"\n")
Port L0 connectDevice failed: asynManager:connectDevice port L0 not found
Which port should I use:
172.20.92.3:80? The 80th? I don't know actually, but in the Tektronix's prefs (Instrument Setup) I see the option
Http Port: 80. Though, I don't know this is the correct port. I presume, it's just for the simple http access via the internet browser. I'm stuck. Please, help!
PAvelOn Mon, Mar 5, 2012 at 6:38 PM, Mark Rivers
<[email protected]> wrote:
Hi Pavel,
This error
ERROR: vxi11Configure is not supported on WIN32
is expected because there is no support for VXI-11 on win32-x86, because we don't have an implementation of Sun RPC for win32-x86, which the VXI-11 support requires.
However, this error:
drvAsynIPPortConfigure("L0", "172.20.92.3", 0, 0, 0)
st.cmd -- Line 50 -- Command drvAsynIPPortConfigure not found.
is not expected. The drvAsynIPPortConfigure command works fine on win32-x86. You must have a mistake in building your application, perhaps you forgot to include "drvAsynIPPort.dbd" in your dbd file.
Mark
________________________________
From: [email protected] [[email protected]] on behalf of Pavel Masloff [[email protected]]
Sent: Monday, March 05, 2012 8:31 AM
To: EPICS Tech Talk; Nicholas P. DiMonte
Subject: TDS 3000 on win32-x86
Hi Nick et al. :
I am trying to use your Tektronix TDS-3000 support on win32-x86. And I have found that it neither works via "Direct network connection" nor "GPIB/LAN connection":
ERROR: vxi11Configure is not supported on WIN32
Is there a possibility to talk to the TDS 3054C device any other way on win32? If so, could you give me a hint?
If using "Remote serial port", the following errors occur:
drvAsynIPPortConfigure("L0", "172.20.92.3", 0, 0, 0)
st.cmd -- Line 50 -- Command drvAsynIPPortConfigure not found.
asynOctetSetInputEos("L0",0,"\n")
Port L0 connectDevice failed: asynManager:connectDevice port L0 not found
asynOctetSetOutputEos("L0",0,"\n")
Port L0 connectDevice failed: asynManager:connectDevice port L0 not found
--
Best regards,
Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia
Mobile: +7 (951) 672 22 19
Phone: +7 (812) 461 01 01
--
Best regards,
Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia
Mobile: +7 (951) 672 22 19