1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: EPICS support for Granville Phillips Series 307 Vacuum Gauge Controller
From: Dirk Zimoch <[email protected]>
To: [email protected]
Cc: [email protected]
Date: Fri, 14 Oct 2011 16:26:28 +0200
Hi Linda,

According to the manual it should be quite straight forward to get it working:


Terminator = CR LF;

# pass gauge number 1 or 2 as parameter
# connect to ai record, use pressure(1) or pressure(2) in INP
pressure { out "DS IG\$1"; in "%f"; }

# connect to bo record, use switch(1) or switch(2) in OUT
switch {out "IG\$1"; in "OK"; }

# connect to bi record
degas_status { out "DGS"; in "%b"; }

# connect to bo records
degas { out "DG %{OFF|ON}"; in "OK";
  @init {degas_status}
}

Similar for all other commands. There are not that many. You don't need to take care of the error strings because no error should happen if the protocols are correct.

I would scan the input record with 1 second.

Cheers,
Dirk


[email protected] wrote:
Is there EPICS support available for the Granville Phillips Series 307 Vacuum Gauge Controller?

Something based on StreamDevice would be ideal but information about any existing support would be appreciated.

Thanks,

Linda Pratt

Software Systems Engineer

Controls Department

[email protected]

+44 (0)1235 778058

www.diamond.ac.uk

Diamond Light Source Ltd

Diamond House

Harwell Science and Innovation Campus

DIDCOT

Oxfordshire

OX11 0DE

UK


--

This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail. Any opinions expressed within this e-mail are those of the individual and not necessarily of Diamond Light Source Ltd. Diamond Light Source Ltd. cannot guarantee that this e-mail or any attachments are free from viruses and we cannot accept liability for any damage which you may sustain as a result of software viruses which may be transmitted in or with the message. Diamond Light Source Limited (company no. 4375679). Registered in England and Wales with its registered office at Diamond House, Harwell Science and Innovation Campus, Didcot, Oxfordshire, OX11 0DE, United Kingdom



References:
EPICS support for Granville Phillips Series 307 Vacuum Gauge Controller Linda.Pratt

Navigate by Date:
Prev: Re: EPICS support for Granville Phillips Series 307 Vacuum Gauge Controller Mohan Ramanathan
Next: Re: EPICS support for Granville Phillips Series 307 Vacuum Gauge Controller Tim Mooney
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: EPICS support for Granville Phillips Series 307 Vacuum Gauge Controller Tim Mooney
Next: RE: EPICS support for Granville Phillips Series 307 Vacuum Gauge Controller Linda.Pratt
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·