1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Alarm Handler and $ALARMCOUNTFILTER
From: <[email protected]>
To: <[email protected]>
Date: Mon, 18 Jul 2011 15:34:58 +0000

Hello,

Please can someone clarify the effects of using the following command in the Alarm Handler configuration file as the user guide does not seen to fully explain the behaviour and it doesn’t seem to do what I want.

 

$ALARMCOUNTFILTER inputCount inputSeconds

 

The documentation says, the channel must remain in alarm for more than inputSeconds or enter into an alarm state more than inputCount times within inputSeconds.

To me these two conditions seem contradictory. If I only want to recognise an alarm that has persisted for inputSeconds then I want to ignore intermittent changes, not count them and go into alarm anyway.

 

My requirement is to only register an alarm if the value exceeds the threshold persistently for 120 seconds.

Is there a recommended trick with the settings to get the alarm handler to do this? Perhaps setting the inputCount to a very high value, so it can’t possibly be exceeded within the time.

 

The other behaviour I’ve noticed is that once in alarm, the same criteria is used to decide when to drop down to no alarm.

i.e. if the PV value drops below the threshold then it takes inputSeconds before this is recognised, or inputCount drops within inputSeconds.

I am just curious as to whether this is behaviour that anybody wants or uses? I’d prefer to drop out of the alarm state immediately.

 

Again, I’d say that the documentation could be clearer and state that these settings relate to transition both into or out of alarm. It does not have any effect for transitions between MINOR and MAJOR alarm states, which occur instantly.

 

Any corrections to my understanding or suggestions to achieve the behaviour I want, would be most appreciated.

 

Thanks,

Keith Baker

 

Diamond Light Source Limited


 

-- 

This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail.
Any opinions expressed within this e-mail are those of the individual and not necessarily of Diamond Light Source Ltd.
Diamond Light Source Ltd. cannot guarantee that this e-mail or any attachments are free from viruses and we cannot accept liability for any damage which you may sustain as a result of software viruses which may be transmitted in or with the message.
Diamond Light Source Limited (company no. 4375679). Registered in England and Wales with its registered office at Diamond House, Harwell Science and Innovation Campus, Didcot, Oxfordshire, OX11 0DE, United Kingdom
 



Replies:
Re: Alarm Handler and $ALARMCOUNTFILTER Andrew Johnson

Navigate by Date:
Prev: Re: EPICS OSI and events Ralph Lange
Next: Re: EPICS OSI and events Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: EPICS OSI and events michael.abbott
Next: Re: Alarm Handler and $ALARMCOUNTFILTER Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·