1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Alarm Handler Configuration
From: "Allison, Stephanie" <[email protected]>
To: Keiko Ezawa <[email protected]>, "[email protected]" <[email protected]>
Date: Mon, 11 Apr 2011 14:05:18 -0700
Hi Keiko,

UP and DOWN refer to the direction that the alarm severity (0 to 3) of the PV or group is changing.  NO_ALARM (0) is the lowest and INVALID_ALARM (3) the highest.  So DOWN_MAJOR will only activate the command when the severity changes from INVALID to MAJOR.  UP_MAJOR only activates the command when the change is from NO_ALARM to MAJOR or MINOR to MAJOR.  

Stephanie Allison

> -----Original Message-----
> From: [email protected] [mailto:[email protected]] On Behalf
> Of Keiko Ezawa
> Sent: Monday, April 11, 2011 11:41 AM
> To: [email protected]
> Subject: Alarm Handler Configuration
> 
> Hello,
> 
> I am trying to configure the alarm handler to send a notification to a pager by using
> $SEVRCOMMAND. I have a channel, IG1:STATON, and when it is turned off or tripped
> off, the alarm handler alarms. However, I don't get the notification to my pager.
> 
> $SEVRCOMMAND DOWN_MAJOR send_alhmail.pl [email protected] 555 1
> 
> When I change DOWN_MAJOR to UP_MAJOR, I receive a notification. Could someone
> please explain when/how to use UP_MAJOR and DOWN_MAJOR?
> 
> Thank you very much,
> 
> Keiko



References:
Alarm Handler Configuration Keiko Ezawa

Navigate by Date:
Prev: Alarm Handler Configuration Keiko Ezawa
Next: Re: vxworks BSP sysBusToLocalAdrs not support PCI space Dirk Zimoch
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Alarm Handler Configuration Keiko Ezawa
Next: How to execute CSS/BOY directly in OPIruntime mode ? patard
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·