Thank you Ralph, Interesting.
Zen
> -----Original Message-----
> From: [email protected] [mailto:[email protected]]
> On Behalf Of Ralph Lange
> Sent: Monday, March 28, 2011 1:29 AM
> To: EPICS Tech Talk
> Subject: Re: asynPortDriver Question
>
> On 27.03.2011 00:11 Mark Rivers wrote:
> > Hi Zen,
> >
> > I don't think you can do that. The first order problem is that there is no
> connection from the asyn driver to the AO:SC record, since it uses soft device
> support, not asyn device support. I don't think there is a way to propogate
> alarm status between records at the database level except by using the MS
> qualifier on input and output links. But I'm not a database programming expert,
> perhaps there is a way to do this.
>
> You can point any unused input link of your "target" record to a field in your
> "source" record and make it "MS" to pull the severity from the
> "source". I know people that are regularly abusing the SIML input link to
> achieve this....
>
> HTH,
> Ralph
- References:
- asynPortDriver Question Szalata, Zenon M.
- RE: asynPortDriver Question Mark Rivers
- Re: asynPortDriver Question Ralph Lange
- Navigate by Date:
- Prev:
Re: how to build c++ Andrew Johnson
- Next:
RE: 64-bit Channel Archiver james.rowland
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: asynPortDriver Question Ralph Lange
- Next:
how to build c++ yangyong203
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|