Hi Florian,
Looks like a race condition. I have to look in the driver. I fear there
is nothing you can do about it.
How does the communication work? You say you get 64 messages in series.
What do they look like? All like "t68043F34AAA1\r" (only difference in
$(no))? That is the timing of these messages? Do they all come in one
burst? Do you have a link to the device documentation?
Dirk
Florian Feldbauer wrote:
Hello all,
I ran into a problem when reading from a serial device using I/O Intr
processing with streamDevice. I receive 64 messages in series and have
one record for each message.
Now and then I get the error message from epics:
timerQueue INTERNAL ERROR (PANDA:FEMC:PROTO192:THMP:680:CHK:00):
timerExpired() unexpected ioAction None
Any idea how to fix this problem?
This is the db:
record (scalcout, "THMP:$(ID):CHK:$(no)")
{
field (DTYP, "stream")
field (SCAN, "I/O Intr")
field (CALC, "((K XOR L) XOR C)==E?(K<<8)+L:LL")
field (OUT, "@THMP.proto getMsg($(no)) USBCAN1")
field (INPC, "$(no)")
field (INLL, "INV CHK")
}
This is the protocol:
Terminator = CR;
getMsg{
in "t6804\${2}%(K)2X%(L)2X%(E)2X";
}
This is an example string, which is sent from the device:
t68043F34AAA1\r
Best regards
Florian
- Replies:
- Re: Problem with streamDevice and I/O Intr Florian Feldbauer
- References:
- Problem with streamDevice and I/O Intr Florian Feldbauer
- Navigate by Date:
- Prev:
Re: VxWorks and Radius Authentication Eric Norum
- Next:
RE: checkRelease on Windows ulrik.pedersen
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Problem with streamDevice and I/O Intr Florian Feldbauer
- Next:
Re: Problem with streamDevice and I/O Intr Florian Feldbauer
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|