On Thursday 15 April 2010, Dirk Zimoch wrote:
> I used an (unofficial) Soft Channel support (attached).
Note that your soft device support sets NORD, but this field is nowhere used
in the record support. So, setting NORD might not do what you expect.
Indeed, when the record's VAL field gets written, EPICS base calls
put_array_info which assigns the number of elements you receive to NELM.
This is also something you probably do not expect to happen. If someone
feels like fixing the aai/o records, this should be on the list, too.
Cheers
Ben